83
Settings for energy saving
Energy saving
Restricting the range of set temperatures
[Set
temperature range limit]
Restrict the range of temperatures that can be set by setting upper and lower limits on temperatures.
4
Change the settings.
Item
Explanation
High limit
Low limit
Set the upper temperature and lower
temperature for “Heat”, “Cool”, and “Auto”.
Set the temperature with
and
.
The setting ranges are as follows.
y
In heating mode:
16 to 30 °C*
1
(1 °C intervals)
*1 The upper limit temperature for
some models is 26 °C.
y
In cooling (drying) mode:
18 to 30 °C (1 °C intervals)
y
In automatic mode:
17 to 27 °C (1 °C intervals)
Note
y
The temperature range you can set
depends on the model.
Temp range limit
The temperature range limit function is
enabled for the selected indoor unit if you
put a check mark here.
Continued on next page
1
Touch [Energy saving] in “EnergySaving”.
1
2
Touch [Set temperature range limit].
z
Enter the identification number (password level 1 or 2) and
the “Set temp. range limit” screen is displayed.
2
3
Put a check mark in the “Select” column
(3-1), and touch [Set.] (3-2).
z
The “Setting” dialogue is displayed.
3-
1
3-
2