IN QUESTION COMPLIES WITH THE STANDARD FOR EMERGENCY CALL SYSTEMS FOR
ASSISTED LIVING AND INDEPENDENT LIVING FACILITIES, UL 2560.
IT IS REQUIRED THAT ONE OF THE CALL INITIATION STATIONS ASSIGNED TO EACH
RESIDENT APARTMENT SHOULD BE PERMANENTLY LOCATED IN THE BATHROOM OF
THAT APARTMENT.
AT LEAST ONE OF THE CALL INITIATION STATIONS SERVING THE PROPERTY MUST BE
PERMANENTLY ATTACHED OR TETHERED AT A FIXED LOCATION.
THE EMERGENCY CALL SYSTEM MUST NOT SHARE ITS COMMUNICATION NETWORK
WITH ANY OTHER NETWORK OR SYSTEM. ALL DEVICES CONNECTED DIRECTLY TO
THE WIRING OF A HARDWIRED SYSTEM, AND ALL TRANSMITTERS USING THE SAME
FREQUENCY OR CHANNEL AND THAT ARE WITHIN RANGE OF A RECEIVER OF A
WIRELESS SYSTEM, MUST BE COMPATIBLE WITH THE EMERGENCY CALL SYSTEM AND
EVALUATED FOR THE INTENDED PURPOSE. SUPPLEMENTARY DEVICES NOT
EVALUATED FOR THE INTENDED PURPOSE ARE PERMITTED ONLY IF THEIR
CONNECTION TO THE NETWORK UTILIZES A COMPATIBLE DEVICE EVALUATED FOR
THE PURPOSE.