Explain the installation and operation of the boiler to the customer or user.
WARNING: Damage to the system due to non-compliance with the minimum return temperature!
During the first start-up, set the minimum return temperature and check it at the boiler return.
During the first start-up, check whether the heating system is filled with water and vented.
During the first start-up, check whether the occurring water pressure is sufficient for thermal
outflow protection (recommended accessory).
Check the thermal outflow protection (recommended accessory).
Set the return temperature raising system to 65 ˚C.
Refer to the instruction manual of the controller to learn about the ignition and control of the
boiler.
7. OPERATION
7.1. Turning on the device
In order to exclude any possible factory defects and defects related to improper connection, the first two
or three runs should be made by an installer in the presence of the user.
After correct installation performed solely by an authorized installer, the boiler can be turned on. In order
to do that, use the temperature controller as described in this document. Full description of the
temperature controller is contained in the temperature controller manual RK- 2006 LPG or RK -2006 SPGM
(separate attachment).
Exercise caution during the first start-up. Pay attention to:
- Check whether the device is connected to power.
- If the burner works in “maximum power” mode and the temperature on the display does not rise for a
few minutes, press STOP on the controller – the message “PUTTING OUT” (or “AFTERBURNING”,
depending on the version) will appear. If the controller does not respond, disconnect the device from
power. In both cases, contact the service technician.
- If the burner works in “maximum power” mode and the temperature on the display rises, the central
heating or hot usable water pump (depending on the operation mode) should start when the displayed
temperature is not higher than 42°C.
If, for some reason, none of the pumps is turned on in the cases described below, immediately put down
the boiler by pressing STOP and contact your installer. If the device does not respond to pressing STOP,
unplug it. This is the final solution, as oxides can accumulate in the burning chamber. After such a
sudden unplugging from the mains, do not turn on the device again and contact the service technician.
DANGER!!! Mortal danger. IF YOU WANT TO TURN OFF THE DEVICE – USE THE STOP BUTTON ON
THE CONTROL PANEL. DO NOT UNPLUG IT BECAUSE OF THE RISK OF EXPLOSION.