PART 2: CX-Server PLC Tools
CHAPTER 4 – PLC Setup Component
OMRON
CX-Server PLC Tools_Page 32
♦
Mode 3. Displays a 4-character message when the IODP (189) instruction is executed in the
unit’s program.
5.
Check the
Automatically Transfer User Program
setting to automatically transfer the user
program from one of the PLCs memory cards when the PLC starts-up.
6.
Check the
Display modes at startup
setting to display all selected modes on startup.
Error Log
The
Error Log
tab permits certain settings to be applied to error logging. Either Data Memory (DM) or
Extended Memory (EM) areas can be selected to hold the PLC’s Error Log. Refer to
Chapter 6 - PLC Error
Component
for a description of the Error Log. Use the following procedure to apply settings in the
Error Log
tab.
1, 2, 3…
1. Check
the
Enable Error Log
setting to enable error logging. If this is not selected, the
default log auxiliary memory is assigned.
2. Enter
the
Start Address
setting for the error log. This is only enabled if the
Enable Error
Log
setting has been selected.
3. Enter
the
EM Bank Number
setting if the Error Log is to be stored on an installed
Extended Memory Card. The
Start Address
setting needs to be set to the relevant area of
EM. This is only enabled if the
Enable Error Log
setting has been selected.
4. Enter
the
Number of Records
setting for the number of records to be held in the PLC Error
component.
Note:
An Error Log in the Auxiliary Area (words A100-A199 for CV1000) can contain up
to 20 error records. To increase the size of the log (to 2047 records), move it to
either the DM or EM areas.
Execution Controls
Instructions can be executed and peripheral servicing performed by either using:
♦
Event driven (asynchronous) processing mode. The peripheral servicing process interrupts the execution
process cycle by sending IO refresh requests.
or
♦
Synchronised processing mode. The execution and peripheral servicing processes wait for each other to
complete the task in hand.
Consult the PLC operational manual for details when defining the execution controls. Use the following
procedure to apply settings in the
Execution Controls
tab.
1, 2, 3…
1. An operand can be indirectly addressed via the DM area in either Binary or BCD. Select
the
Binary
setting or the
BCD
setting as required.
2. Set
the
Step Timer
setting for the SFC step instructions. The default is 0.1s.
Note:
For CV1000, CV2000 and CVM1/CPU21-EV2 PLCs, EM can be used for indirect
addressing of an operand.
Note:
The
Step
Timer setting is not available to CVM1 PLCs.
Execution Controls 1
Use the following procedure to apply settings.
1, 2, 3…
1. Check
the
Measure CPU-Bus Unit Cycle
setting for the CPU to measure the service cycle.
2. Check
the
Detect Low Battery
setting to flag PLC and Memory Card low battery.
3. Check
the
CPU standby on initialisation of bus units
setting to ensure the CPU remains in
standby until SYSMAC BUS/2 terminators are detected. If this is not checked, PLC
operation begins regardless of the presence of terminators.
4. Check
the
Error on power off interrupts
setting to ignore a momentary power interruption
(and not generate an error) or leave unchecked to generate an error on power off.
Execution Controls 2
Check the following settings as required.
♦
The Duplication action error setting.
Содержание Sysmac WS02-CXPC1-EV3
Страница 1: ...Cat No W414 E1 01 SYSMAC...
Страница 2: ......
Страница 3: ...SYSMAC WS02 CXPC1 EV3 CX Programmer Ver 3 1 Operation Manual Revised November 2002...
Страница 4: ......
Страница 6: ......
Страница 7: ...PART1 CX Programmer...
Страница 8: ......
Страница 24: ......
Страница 34: ......
Страница 106: ......
Страница 130: ......
Страница 131: ...PART 2 CX Server PLC Tools...
Страница 132: ......
Страница 136: ......
Страница 158: ......
Страница 168: ......
Страница 194: ......
Страница 206: ......
Страница 250: ......
Страница 298: ......
Страница 304: ......
Страница 305: ...PART 3 CX Server Runtime...
Страница 306: ......
Страница 310: ......
Страница 338: ......
Страница 344: ......
Страница 378: ......
Страница 384: ......
Страница 388: ......
Страница 390: ...Cat No W414 E1 01 Note Specifications subject to change without notice Printed in Japan Authorized Distributor...