306
Conversion Instructions
Section 5-20
The following table shows the functions and ranges of the parameter words:
The following diagram shows the source word, S, converted to D according to
the line defined by points (A
Y
, A
X
) and (B
Y
, B
X
).
The results can be calculated by first converting all values to BCD and then
using the following formula.
Results = B
Y
– [(B
Y
– A
Y
)/(B
X
– A
X
) X (B
X
– S)]
Flags
ER:
The value in P1+1 equals that in P1+3.
Indirectly addressed EM/DM word is non-existent.
(Content of
*
EM/
*
DM word is not BCD, or the EM/DM area boundary
has been exceeded.)
P1 and P1+3 are not in the same data area, or other setting error.
EQ:
ON when the result, R, is 0000.
Example
When 00000 is turned ON in the following example, the BCD source data in
DM 0100 (#0100) is converted to hexadecimal according to the parameters in
DM 0150 to DM 0153. The result (#0512) is then written to DM 0200.
Parameter
Function
Range
Comments
P1
BCD point #1 (A
Y
)
0000 to 9999
---
P1+1
Hex. point #1 (A
X
)
0000 to FFFF
Do not set P1+1=P1+3.
P1+2
BCD point #2 (B
Y
)
0000 to 9999
---
P1+3
Hex. point #2 (B
X
)
0000 to FFFF
Do not set P1+3=P1+1.
A
X
S
B
X
Value after conversion
(BCD)
B
Y
R
Value before conversion
(Hexadecimal)
A
Y
@SCL(66)
DM 0150
DM 0100
00000
DM 0200
Address Instruction
Operands
00000
LD
00000
00001
@SCL(66)
DM
0100
DM
0150
DM
0200
DM 0150 0010
DM 0151 0005
DM 0152 0050
DM 0153 0019
DM 0100 0100
DM 0200 0512
Содержание SYSMAC CQM1H Series
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ......
Страница 11: ......
Страница 15: ...xvi...
Страница 87: ...62 Calculating with Signed Binary Data Section 1 7...
Страница 169: ...144 Serial Communications Board Section 2 6...
Страница 537: ......
Страница 565: ......
Страница 569: ......
Страница 573: ......
Страница 577: ......