156
IR Area
Section 3-2
Note
Applicable only for CQM1H-SCB41, lot numbers 0320 or later.
High-speed Counter Board Flags/Bits
IR 205 00 to 03
Port 1
Completed Reception Case Number
R
Protocol macro
04 to 07
Completed Step Number
R
08 to 14
Not used.
R
15
IR 20408 to IR 20411 Data Stored Flag
0: No data stored; 1: Data stored
R
IR 206 00 to 03
Port 2
Completed Reception Case Number
R
Protocol macro
04 to 07
Completed Step Number
R
08 to 14
Not used.
R
15
IR 20412 to IR 20415 Data Stored Flag
0: No data stored; 1: Data stored
R
IR 207 00
Port 1
Serial Communications Port Restart Bits
W
All modes
01
Port 2
02
Port 1
Continuous Trace Start/Stop Bits
W
Protocol macro
03
Port 2
04
Port 1
Shot Trace Start/Stop Bits
W
05
Port 2
06
Port 1
Echoback Disable Bit
(Only used for modem control in protocol
macro mode. See note.)
W
07
Port 2
08
Port 1
Protocol Macro Executing Flag
R
No-protocol
or
Protocol macro
09
Step Error Processing Flag
R
Protocol macro
10
Sequence End Completion Flag
R
11
Forced Abort Bit
W
12
Port 2
Protocol Macro Executing Flag
R
No-protocol or
Protocol macro
13
Step Error Processing Flag
R
Protocol macro
14
Sequence End Completion Flag
R
15
Forced Abort Bit
W
IR 208
to
IR 215
00 to 15
Not used.
---
---
Word
Bits
Name
Function
Read/
Write
IR 200
00 to 15
High-speed
Counter 1
PV (rightmost 4 digits)
Contains the high-speed counter PV for
each of the High-speed Counter Board’s
ports.
Note
The PV data format (BCD or hexa-
decimal) can be set in the PC Setup
(DM 6602.)
R
IR 201
00 to 15
PV (leftmost 4 digits)
IR 202
00 to 15
High-speed
Counter 2
PV (rightmost 4 digits)
IR 203
00 to 15
PV (leftmost 4 digits)
IR 204
00 to 15
High-speed
Counter 3
PV (rightmost 4 digits)
IR 205
00 to 15
PV (leftmost 4 digits)
IR 206
00 to 15
High-speed
Counter 4
PV (rightmost 4 digits)
IR 207
00 to 15
PV (leftmost 4 digits)
Word
Bits
Function
Read/
Write
Communications
modes
Содержание SYSMAC CQM1H Series
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ......
Страница 11: ......
Страница 15: ...xvi...
Страница 87: ...62 Calculating with Signed Binary Data Section 1 7...
Страница 169: ...144 Serial Communications Board Section 2 6...
Страница 537: ......
Страница 565: ......
Страница 569: ......
Страница 573: ......
Страница 577: ......