4
PC Setup
Section 1-1
1-1-3
PC Setup Settings
The following table shows the PC Setup settings in order in the DM area. For
details, refer to the page numbers shown.
DM 6553
(port 2)
DM 6558
(port 1)
00 to 07
Node Number
(Host Link)
00 to 31 (BCD)
08 to 11
Start Code Enable
(No-protocol)
0: Disable; 1: Set
12 to 15
End Code Enable
(No-protocol)
0: Disable (number of bytes received)
1: Set (specified end code)
2: CR, LF
DM 6554
(port 2)
DM 6559
(port 1)
00 to 07
Start Code
(No-protocol)
00 to FF (hexadecimal)
08 to 15
When bits 12 to 15 of DM 6553 or DM 6558 are set to 0:
Number of Bytes Received
00: Default setting (256 bytes)
01 to FF: 1 to 255 bytes
When bits 12 to 15 of DM 6553 or DM 6558 are set to 1:
End Code
(No-protocol)
00 to FF (hexadecimal)
Word(s)
Bit(s)
Function
Word(s)
Bit(s)
Function
Page
Startup Processing (DM 6600 to DM 6614)
The following settings are effective after transfer to the PC only after the PC is restarted.
DM 6600
00 to 07
Startup Mode
(effective when bits 08 to 15 are set to 02).
00: PROGRAM; 01: MONITOR 02: RUN
12
08 to 15
Startup Mode Designation
00: Depends on CPU Unit DIP switch pin 7 and Programming Console switch settings
01: Continue operating mode last used before power was turned OFF
02: Setting in DM 6600 bits 00 to 07
DM 6601
00 to 07
Not used.
08 to 11
I/O Hold Bit
Status
(SR 25212)
0: Reset; 1: Maintain
13
12 to 15
Forced Status Hold Bit Status
(SR 25211)
0: Reset; 1: Maintain
DM 6602 to
DM 6603
00 to 15
Inner Board Slot 1 Settings
(See
1-2 Inner Board Settings
for details.)
9
DM 6604 to
DM 6610
00 to 15
Not used.
DM 6611 to
DM 6612
00 to 15
Inner Board Slot 2 Settings
(See
1-2 Inner Board Settings
for details.)
9
DM 6613
00 to 15
Servicing Time Setting for Serial Communications Board Port 2
9
DM 6614
00 to 15
Servicing Time Setting For Serial Communications Board Port 1
Pulse Output and Cycle Time Settings (DM 6615 to DM 6619)
The following settings are effective after transfer to the PC the next time operation is started.
DM 6615
00 to 07
Word for Pulse Output
00: IR 100; 01: IR101; 02: IR 102... 15: IR 115
Sets the word used for pulse output from an output on a Transistor Output Unit. Pulses
can be output only from one output at a time.
46
08 to 15
Not used. Set to 00.
Содержание SYSMAC CQM1H Series
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ......
Страница 11: ......
Страница 15: ...xvi...
Страница 87: ...62 Calculating with Signed Binary Data Section 1 7...
Страница 169: ...144 Serial Communications Board Section 2 6...
Страница 537: ......
Страница 565: ......
Страница 569: ......
Страница 573: ......
Страница 577: ......