467
Host Link Commands
Section 6-5
Forced set/Reset/Cancel data (Command)
If a timer or counter completion flag is specified, only bit 15 is effective and all
other bits will be ignored. Only force-setting and force-resetting are possible
for timers/counters.
If a word address is specified, the content of the word specifies the desired
process for each bit in the specified word, as shown in the following table.
The bits that are merely set or reset may change status the next time the pro-
gram is executed, but bits that are force-set or force-reset will maintain the
forced status until it is cleared.
Response Format
An end code of 00 indicates normal completion.
6-5-29 FORCED SET/RESET CANCEL –– KC
Cancels all forced set and forced reset bits (including those set by FORCED
SET, FORCED RESET, and MULTIPLE FORCED SET/RESET). If multiple
bits are set, the forced status will be cancelled for all of them. It is not possible
to cancel bits one by one using KC.
Command Format
Response Format
An end code of 00 indicates normal completion.
6-5-30 PC MODEL READ –– MM
Reads the model type of the PC.
Command Format
BCD setting
Process
0
No action (bit status not changed)
2
Reset
3
Set
4
Forced-reset
5
Forced-set
8
Forced set/reset status cancel
@
F
K
x 10
0
x 10
1
x 16
1
x 16
0
↵
*
Node
No.
Header
code
Terminator
FCS
End code
@
K
C
x 10
0
x 10
1
↵
*
Node No.
Header
code
Terminator
FCS
@
K
C
x 10
0
x 10
1
x 16
1
x 16
0
↵
*
Node
No.
Header
code
Terminator
FCS
End code
@
M
M
x 10
0
x 10
1
↵
*
Node
No.
Header
code
Terminator
FCS
Содержание SYSMAC CQM1H Series
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ......
Страница 11: ......
Страница 15: ...xvi...
Страница 87: ...62 Calculating with Signed Binary Data Section 1 7...
Страница 169: ...144 Serial Communications Board Section 2 6...
Страница 537: ......
Страница 565: ......
Страница 569: ......
Страница 573: ......
Страница 577: ......