Host Link Commands
Section 6-5
Response Format
An end code of 00 indicates normal completion.
Parameters
Model Code
“Model code” indicates the PC model in two digits hexadecimal.
6-5-31 TEST–– TS
Returns, unaltered, one block of data transmitted from the host computer.
Command Format
Response Format
An end code of 00 indicates normal completion.
Parameters
Characters (Command, Response)
For the command, this setting specifies any characters other than the carriage
return (CHR$(13)). For the response, the same characters as specified by the
command will be returned unaltered if the test is successful.
@
M
M
x 10
0
x 10
1
x 16
1
x 16
0
↵
*
x 16
1
x 16
0
Node
No.
Header
code
Terminator
FCS
End code
Model
code
Model code
Model
01
C250
02
C500
03
C120
0E
C2000
10
C1000H
11
CQM1H/C2000H/CQM1/CPM1/CPM1A/CPM2A/CPM2C/SRM1
12
C20H/C28H/C40H/C200H/C200HS
20
CV500
21
CV1000
22
CV2000
40
CVM1-CPU01-E
41
CVM1-CPU11-E
42
CVM1-CPU21-E
@
T
S
x 10
0
x 10
1
*
↵
Node No.
Header
code
Characters
122 characters max.
Terminator
FCS
@
T
S
x 10
0
x 10
1
*
↵
Node No.
Header
code
Characters
122 characters max.
Terminator
FCS
Содержание SYSMAC CQM1H Series
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ......
Страница 11: ......
Страница 15: ...xvi...
Страница 87: ...62 Calculating with Signed Binary Data Section 1 7...
Страница 169: ...144 Serial Communications Board Section 2 6...
Страница 537: ......
Страница 565: ......
Страница 569: ......
Страница 573: ......
Страница 577: ......