541
Appendix D
Using the Clock
The CQM1H PCs can be equipped with a clock by installing a Memory Cassette with a clock. This section
explains how to use the clock.
There is an “R” at the end of the model number of Memory Cassettes with a built-in clock. For example, the
CQM1-ME04R Memory Cassette has a built-in clock. Refer to
3-11 Using Memory Cassettes
for a list of avail-
able Memory Cassettes.
Note
The clock will stop and the current date and time clock data will be lost if the Memory Cassette is
removed from the CPU Unit.
The accuracy of the clock depends on and ambient temperature, as shown in the following table.
Words Containing the Date and Time
The following illustration shows the configuration of the words (AR 17 through AR 21) that are used with the
clock. These words can be read and used as required. (AR 17 is provided so that the hour and minute can be
accessed quickly.)
Setting the Time
To set the time, use a Programming Device as follows:
Note
The time can be set easily using menu operations from a Programming Device such as a Programming
Console. Refer to the
CQM1H Operation Manual
for the Programming Console procedure.
Setting Everything
Set the time and date with the following procedure:
1,2,3...
1.
Turn ON AR 2114 (Clock Stop Bit) to stop the clock and allow AR 18 through AR 21 to be over-
written.
2.
Using a Programming Device, set AR 18 through AR 20 (minute/second, date/hour, and year/
month) and AR 2100 through AR 2107 (day of week).
3.
Turn ON AR 2115 (Clock Set Bit) when the time set in step 2 is reached. The clock will start
operating from the time that is set, and the Clock Stop Bit and Clock Set BIt will be turned OFF
automatically.
Ambient temperature
Accuracy by month
55
°
C
–3 to 0 min
25
°
C
±
1 min
0
°
C
–2 to 0 min
15
8 7
0
AR 18
AR 19
AR 20
AR 21
Minute
Date
Second
Hour
Year
Month
Day of week
2 digits BCD each.
(Only the last 2 digits of the
year are displayed.)
00 to 06: Sunday to Saturday
AR 2115 Clock Set Bit
AR 2114 Clock Stop Bit
AR 2113 30-Second Adjustment Bit
Hour
Minute
AR 17
Содержание SYSMAC CQM1H Series
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ......
Страница 11: ......
Страница 15: ...xvi...
Страница 87: ...62 Calculating with Signed Binary Data Section 1 7...
Страница 169: ...144 Serial Communications Board Section 2 6...
Страница 537: ......
Страница 565: ......
Страница 569: ......
Страница 573: ......
Страница 577: ......