7-3 Troubleshooting and Maintenance
7-10
Message Cause
Possible countermeasure
WARNING No. 22: Memory
Card Error: Some files in a
memory card may be cor-
rupted. Safely remove the
memory card, and check
whether files are not cor-
rupted on a computer.
You can continue to startup
the PT by touching on the
screen, however, it may
NOT operate correctly when
accessing to the memory
card. (The same message
will also be displayed in
Japanese. This is not a
fault.)
The two following causes
are possible:
The previous time the PT
was used, power was turned
OFF while accessing the
Memory Card.
Memory Card access safety
information could not be
held because the battery
was connected or there was
insufficient capacity.
Touch the touch panel to continue
booting. When the Memory Card is
accessed, however, the PT may not
operate normally.
WARNING No. 23: Screen
data file(s) is not correct:
Touch the screen to con-
tinue and transfer screen
data again.
The PT screen data is cor-
rupted. (The cable was dis-
connected or the power was
turned OFF during screen
data transfer).
Touch the PT’s touch panel, and after
connecting
is displayed at the bottom
right of the screen, or after the mes-
sage "No project data is registered.
Press OK button and download pro-
ject data." is displayed, reattempt
screen transfer.
WARNING No. 24: The re-
covery program in the in-
serted Memory Card is not
supported by the PT. Update
the recovery program, refer-
ring to NS Series Setup
Manual. To continue starting
the PT without executing the
program, touch the screen.
The recovery program can-
not be started because the
recovery program installer in
the Memory Card that is
inserted in the PT is not
supported by the current
hardware version of the PT.
Touch the screen to start the system
that is currently installed in the PT
(i.e., not the recovery program). To
start the recovery program that is in
the Memory Card, you must update
the recovery program that is stored in
the Memory Card. To update the pro-
gram, install the CX-Designer in a
personal computer and then select
Programs - OMRON - CX-One –
CX-Designer – How to recover or
update the system program
from
the Window's Start Menu.
Errors while Connecting to the Host
Symptoms at
PT
Cause Possible
countermeasure
The settings for
Ethernet connection,
such as node number,
network number, and
IP address, are not
set correctly.
Set the settings correctly, referring to
Section 5 Connect-
ing to Host via Ethernet or Controller Link
.
The protocol settings
for the host and the
settings at the PT do
not match.
Set the communications settings using the CX-Designer.
The PT is not con-
nected to the host
properly.
Check that the type, length, and wiring of the connecting
cables meet the specifications.
(Refer to
Section 4 Connecting the Host to Serial Port
.)
PT cannot
communicate
with the host.
(An error mes-
sage is dis-
played or
con-
necting
is dis-
played at the
bottom right of
the screen.)
For 1:N NT Link con-
nections, two or more
Units have the same
unit number.
Reset so that each Unit has a unique unit number.
(Refer to
6-6 Communications Settings
.)
Содержание NS15-V2 Series
Страница 1: ...Cat No V083 E1 14 Programmable Terminals NS Series SETUP MANUAL...
Страница 2: ......
Страница 34: ...1 4 Procedure for Running NS series PTs 1 12...
Страница 54: ...2 2 Part Names and Functions 2 20...
Страница 144: ...4 4 Recommended Connector Cables 4 28...
Страница 174: ...5 3 Connecting to Host via EtherNet IP 5 30...
Страница 196: ...6 3 PT Settings 6 22 PT Tab Page for the NS10 and NS8 Page 1 Page 2 Page 3 Page 4 PT Tab Page for the NS5 Page 1 Page 2...
Страница 246: ...6 11 Verifying Tags 6 72...
Страница 280: ...Appendix 2 Dimensions A 20 NS5 V1 V2 Cable Connection Dimensions...
Страница 333: ......
Страница 334: ......