3-8 Installing the Controller Link Interface Unit
3-54
3-8-4 Wiring
This section describes the method for wiring the network communications cable to the Con-
troller Link Support Board.
z
Wiring the Communications Cable
Wire the communications cable to connect identical signals.
Precautions
for Safe Use
•
Use the cable specified for the communications cable.
•
Keep communications cables separated from power lines or high-tension
lines to prevent influences from electronic noise.
•
Ground the shield of the communications cable at one end of the network.
Do not ground the shield at both ends.
•
Do not connect the shield cable of the communications cable to a ground
that is also being used for power-system devices, such as inverters.
•
Do not run wiring outdoors. If outdoor wiring is necessary, take protective
measures against lightening, such as underground wiring or wiring inside
pipes.
•
Always turn OFF the power to PT before connecting the communications
cable or installing/removing the connector.
•
Use the connector attached to the Controller Link Support Board.
Connecting the Communications Cable
Connect the communications cable to the Controller Link Support Board after first connect-
ing it to the cable connector provided.
Use one of the twisted-pair cables listed below as the communications cable.
Model Manufacturer
Remarks
Li2Y-FCY2x0.56qmm KROMBERG & SHUBERT, De-
partment KOMTEC
German company
1x2xAWG-20PE+Tr.
CUSN+PVC
DRAKA CABLES INDUSTRIAL
Spanish company
#9207 BELDEN
American
company
ESVC0.5x2C
Bando Densen Co.
Japanese company
ESNC0.5×2C-99-
087B
Nihon Electric Wire & Cable Co. Japanese company
Precautions
for Safe Use
•
Use the cables listed above.
•
Normal communications may not be possible if a communications cable
other than those listed above is used.
Reference
•
Terminals for the same signal on the Controller Link Support Board’s connector are
connected internally.
•
The thickness of the ground wire connected to the Controller Link Support Board’s
connector must be less than 2.5 mm
2
.
•
Connect to the network using the special connector provided with the Controller Link
Interface Unit.
Содержание NS15-V2 Series
Страница 1: ...Cat No V083 E1 14 Programmable Terminals NS Series SETUP MANUAL...
Страница 2: ......
Страница 34: ...1 4 Procedure for Running NS series PTs 1 12...
Страница 54: ...2 2 Part Names and Functions 2 20...
Страница 144: ...4 4 Recommended Connector Cables 4 28...
Страница 174: ...5 3 Connecting to Host via EtherNet IP 5 30...
Страница 196: ...6 3 PT Settings 6 22 PT Tab Page for the NS10 and NS8 Page 1 Page 2 Page 3 Page 4 PT Tab Page for the NS5 Page 1 Page 2...
Страница 246: ...6 11 Verifying Tags 6 72...
Страница 280: ...Appendix 2 Dimensions A 20 NS5 V1 V2 Cable Connection Dimensions...
Страница 333: ......
Страница 334: ......