7-3 Troubleshooting and Maintenance
7-12
Symptoms at
PT
Cause Possible
countermeasure
Screens are
slow to
change.
Communications
are not possible
with the host.
If a communications error is displayed, refer to
5-2-7 Com-
munication Errors and Countermeasures
in the
NS Series
Programmable Terminals PROGRAMMING MANUAL
(Cat. No. V073).
Communications errors will not be displayed if automatic
recovery is set for communications. If automatic recovery is
set, check if communications with the host are possible
using the communications test on the System Menu. If
more than one host is registered, test communications with
all of the hosts.
PT has malfunc-
tioned due to exter-
nal noise.
Reset the PT, and wire it according to noise prevention
measures.
The touch
panel does not
respond.
The touch panel is
damaged.
Test the touch panel using the hardware check in the Sys-
tem Menu. If an error has occurred, contact your nearest
OMRON representative.
The brightness set-
ting is too low.
Increase the backlight brightness in the PT Tab Page of the
System Menu.
The display is
dark.
The backlight is
faulty or its service
life has expired.
The backlight must be replaced. Contact your nearest
OMRON representative.
The communica-
tions settings are
incorrect.
When using the device monitor, set the communications
mode as follows:
•
C-series PLCs:
1:1 NT Link or 1:N NT Links
•
CS1-series PLCs:
1:N NT Links (normal, high speed)
The device monitor function is not supported for Ethernet or
Controller Link.
Cannot enter
the device
monitor func-
tion.
The PLC does not
support the device
monitor function.
The PLCs that support the device monitor function are re-
stricted. Check the PLC model being used.
(Refer to
6-8-4 Device Monitor.
)
Errors during Object Operation
Symptoms at
PT
Cause Possible
countermeasure
Communications
are unstable due to
external noise.
Perform noise countermeasures such as separating com-
munications cables from power lines.
There are too many
Numeral Display &
Input objects and
String Display &
Input objects in the
display.
Reduce the number of Numeral Display & Input and String
Display & Input objects in the screen where update is slow.
The numerical
and character
string update
is slow.
For RS-422A com-
munications, the
branch is incorrect
or the terminating
resistance is not set
properly.
Wire correctly, referring to
Appendix 3 Using NS-AL002
Converters
.
Содержание NS15-V2 Series
Страница 1: ...Cat No V083 E1 14 Programmable Terminals NS Series SETUP MANUAL...
Страница 2: ......
Страница 34: ...1 4 Procedure for Running NS series PTs 1 12...
Страница 54: ...2 2 Part Names and Functions 2 20...
Страница 144: ...4 4 Recommended Connector Cables 4 28...
Страница 174: ...5 3 Connecting to Host via EtherNet IP 5 30...
Страница 196: ...6 3 PT Settings 6 22 PT Tab Page for the NS10 and NS8 Page 1 Page 2 Page 3 Page 4 PT Tab Page for the NS5 Page 1 Page 2...
Страница 246: ...6 11 Verifying Tags 6 72...
Страница 280: ...Appendix 2 Dimensions A 20 NS5 V1 V2 Cable Connection Dimensions...
Страница 333: ......
Страница 334: ......