6-6 Communications Settings
6-46
Comm. Speed
Sets the baud rate.
500K, 1M, or 2M
Read Status
Displays whether Controller Link status is read (display
only).
Read Allocation
Add.
Displays address where status is read (display only).
Note: Using the Controller Link network and the network number cannot be changed at the PT. If you
change the setting, display the communications settings in the CX-Designer by selecting
PT –
Communication Setting
, change the setting, and then transfer the project to the PT.
6-6-6
Setting Bar Code Readers
The PT has a Bar Code Reader input function allowing input of barcode data as character
strings in the String Display & Input object.
The methods for setting the communications conditions with the Bar Code Reader are de-
scribed here.
Reference
•
Refer to
3-4 Connecting to Bar Code Readers
for information on methods for connect-
ing Bar Code Readers.
•
The Bar Code Reader can be connected to either serial port A or serial port B only.
Set the communications conditions and confirmation method for the Bar Code Reader using
the following procedure from the System Menu.
Set the Bar Code Reader’s communications method for serial port A or serial port B.
The setting items for the Bar Code Reader will be displayed on the right side of the screen.
Set the Communications speed, data bits, stop bits, parity, and input method.
After setting, press the
Write
Button to save the settings.
•
Setting Communications Conditions for Bar Code Reader Mode
Setting item
Function
Settings
Comm. speed
Sets the communications speed for
communications with the Bar Code
Reader.
4800, 9600, or 19200 (bps)
Data bits
Sets the data bit length.
7 or 8 bits
Stop bits
Sets the data stop bit length.
1 or 2 bits
Parity
Sets the data parity bits.
None, odd, or even
Input method
Sets the confirmation method used after
inputting data in the input column.
Auto or manual confirmation
Continuous input
Sets continuous barcode input to Yes or
No.
Yes or No
Содержание NS15-V2 Series
Страница 1: ...Cat No V083 E1 14 Programmable Terminals NS Series SETUP MANUAL...
Страница 2: ......
Страница 34: ...1 4 Procedure for Running NS series PTs 1 12...
Страница 54: ...2 2 Part Names and Functions 2 20...
Страница 144: ...4 4 Recommended Connector Cables 4 28...
Страница 174: ...5 3 Connecting to Host via EtherNet IP 5 30...
Страница 196: ...6 3 PT Settings 6 22 PT Tab Page for the NS10 and NS8 Page 1 Page 2 Page 3 Page 4 PT Tab Page for the NS5 Page 1 Page 2...
Страница 246: ...6 11 Verifying Tags 6 72...
Страница 280: ...Appendix 2 Dimensions A 20 NS5 V1 V2 Cable Connection Dimensions...
Страница 333: ......
Страница 334: ......