Appendix 1 Specifications
A-3
Appendix 1
Specifications
A-1-1 General
Specifications
Specifications
Item
NS15-TX01
@
-V2
NS12-TS0
@
-V1
NS12-TS0
@
-V2
NS10-TV0
@
-V1
NS10-TV0
@
-V2
NS8-TV
@@
-V1
NS8-TV
0@
-V2
NS5-SQ0
@
-V1
NS5-
S
Q
@@
-V2
NS5-
T
Q
@@
-V2
NS5-
M
Q
@@
-V2
Rated power
supply voltage
24 VDC
Allowable volt-
age range
20.4 to 27.6 VDC (24 VDC
±
15%)
Allowable input
power interrup-
tion time
No restriction.
Power consump-
tion
45 W max.
25 W max
15 W max.
Ambient operat-
ing
temperature
0 to 50
°
C (See notes 1, 2, and 3.)
Storage tempera-
ture
−
20 to 60
°
C (See note 2.)
Ambient operat-
ing
humidity
35% to 85% (0 to 40
°
C) with no condensation
35% to 60% (40 to 50
°
C) with no condensation
Operating envi-
ronment
No corrosive gases.
Noise immunity
Conforms to IEC61000-4-4, 2 KV (power lines)
Vibration resis-
tance
(during opera-
tion)
5 to 8.4 Hz with 3.5
mm single ampli-
tude and 8.4 to
150 Hz with 9.8
m/s
2
acceleration
10 times in each of
X, Y, and Z direc-
tions
10 to 57 Hz with 0.075 mm amplitude and 57 to 150 Hz with 9.8 m/s
2
accelera-
tion for 30 min in each of X, Y, and Z directions
Shock resistance
(during opera-
tion)
147 m/s
2
3 times in each of X, Y, and Z directions.
Dimensions 405
×
304
×
75.8 mm
(W
×
H
×
D)
315
×
241
×
48.5 mm (W
×
H
×
D)
232
×
177
×
48.5 mm
(W
×
H
×
D)
195
×
142
×
54 mm
(W
×
H
×
D)
Panel cutout
dimensions
Width 383.5
+1
0
×
Height
282.5
+1
0
mm
Panel thickness:
1.6 to 4.8 mm
Width 302
+1
0
×
Height
228
+1
0
mm
Panel thickness:
1.6 to 4.8 mm
Width 302
+1
0
×
Height
228
+1
0
mm
Panel thickness:
1.6 to 4.8 mm
Width
220.5
+0.5
0
×
Height 165.5
+0.5
0
mm
Panel thickness:
1.6 to 4.8 mm
Width 184
+0.5
0
×
Height 131
+0.5
0
mm
Panel thickness:
1.6 to 4.8 mm
Weight
4.2 kg max.
2.5 kg max.
2.0 kg max.
1.0 kg max.
Enclosure rating
Front panel: IP65 oil-proof type (equivalent to NEMA4) (See note 4.)
Battery life
5 years (at 25
°
C)
The SRAM and RTC will be backed up for 5 days after the battery runs low (indicator lights orange).
The SRAM and RTC will be backed up by a super capacitor for 5 minutes after removing the old bat-
tery (i.e., after turning ON power after 5 minutes).
International
standards
EC Directives
UL 1604 Class 1 Division 2, EC Directives
Note 1. The operating temperature is subject to the following restrictions, depending on the mount-
ing angle and whether an Expansion Unit is installed or not.
Содержание NS15-V2 Series
Страница 1: ...Cat No V083 E1 14 Programmable Terminals NS Series SETUP MANUAL...
Страница 2: ......
Страница 34: ...1 4 Procedure for Running NS series PTs 1 12...
Страница 54: ...2 2 Part Names and Functions 2 20...
Страница 144: ...4 4 Recommended Connector Cables 4 28...
Страница 174: ...5 3 Connecting to Host via EtherNet IP 5 30...
Страница 196: ...6 3 PT Settings 6 22 PT Tab Page for the NS10 and NS8 Page 1 Page 2 Page 3 Page 4 PT Tab Page for the NS5 Page 1 Page 2...
Страница 246: ...6 11 Verifying Tags 6 72...
Страница 280: ...Appendix 2 Dimensions A 20 NS5 V1 V2 Cable Connection Dimensions...
Страница 333: ......
Страница 334: ......