5-3 Connecting to Host via EtherNet/IP
5-29
•
Connecting to a CJ-series EtherNet/IP Unit
CJ1W-EIP21
Setting the Front Panel Switches
Setting Unit Numbers
Always set the unit numbers so that the unit numbers of other CPU Bus Units mounted to the
same CPU Unit are all unique.
Use a small screwdriver to set the rotary switches, being careful not to damage them.
The factory setting is 0.
Setting range
0 to F
Setting Node Numbers
Set the node numbers as hexadecimal values with the node number setting switch. Always
set the node numbers so that other Ethernet Units connected to the same Ethernet network
all have unique addresses. As long as the addresses are unique, they can be set between 01
and 7E (1 to 126 decimal).
Setting range
01 to 7E (1 to 126 decimal)
Set the upper digit using the left rotary switch and the lower digit using the right rotary switch.
The factory setting is 01.
When using automatic generation to convert addresses, set the node number to the same
value as that of the rightmost byte of the local IP address. If the same values cannot be set,
the IP address table method or combination method must be used to convert the addresses.
Setting Local IP Addresses
Set the local IP address with the CX-Programmer or other computer support software. Refer
to the
EtherNet/IP Unit Operation Manual
(Cat. No. Z909) for details on setting methods.
Ethernet Connectors
This is the connector used to connect the twisted-pair cable to the Ethernet.
•
Electrical Characteristics: Conforms to IEEE802.3 standards.
•
Connector Layout: RJ45 8-pin modular connector (conforms to ISO8877).
Connec-
tor Pin
Signal name
Abbreviation
Signal direction
1
Send data
TD+
Output
2
Send data
−
TD
−
Output
3
Receive data +
RD+
Input
4
Not used.
−
−
5
Not used.
−
−
6
Receive data
−
RD
−
Input
7
Not used.
−
−
8
Not used.
−
−
1
8
Содержание NS15-V2 Series
Страница 1: ...Cat No V083 E1 14 Programmable Terminals NS Series SETUP MANUAL...
Страница 2: ......
Страница 34: ...1 4 Procedure for Running NS series PTs 1 12...
Страница 54: ...2 2 Part Names and Functions 2 20...
Страница 144: ...4 4 Recommended Connector Cables 4 28...
Страница 174: ...5 3 Connecting to Host via EtherNet IP 5 30...
Страница 196: ...6 3 PT Settings 6 22 PT Tab Page for the NS10 and NS8 Page 1 Page 2 Page 3 Page 4 PT Tab Page for the NS5 Page 1 Page 2...
Страница 246: ...6 11 Verifying Tags 6 72...
Страница 280: ...Appendix 2 Dimensions A 20 NS5 V1 V2 Cable Connection Dimensions...
Страница 333: ......
Страница 334: ......