134
Advanced Function Setting Level
Section 5-7
• This parameter sets the output status for alarm 1.
• When “close in alarm” is set, the status of the alarm output function will be
output as is. When “open in alarm” is set, the status of the alarm output
function will be reversed before being output. The following table shows
the relationship between alarm output functions, alarm output and output
LCDs.
• When “open in alarm” is set, the “open in alarm” status is also applied to
heater burnout and HS alarm outputs, and to input error outputs.
Related Parameters
Alarm value 1: Page 101, Alarm value upper limit 1, Alarm value lower limit 1:
Page 103 (operation level)
Alarm 1 type (initial setting level): Page 124
Standby sequence reset: Page 133, Alarm 1 hysteresis: Page 135, Alarm 1
latch: Page 139 (advanced function setting level)
• These parameters set the output status for alarm 2 and alarm 3 settings.
• When “close in alarm” is set, the status of the alarm output function will be
output as is. When “open in alarm” is set, the status of the alarm output
function will be reversed before being output. The following table shows
the relationship between alarm output functions, alarm output and output
LCDs.
al1n
Alarm 1 Open in Alarm
Alarm 1 must be assigned.
Alarm output operation
Alarm output
Output LCDs
Close in alarm ON
ON
Lit
OFF
OFF
Not lit
Open in alarm ON
OFF
Lit
OFF
ON
Not lit
Setting range
Default
n-o
: Close in alarm,
n-c
: Open in alarm
n-o
Setting
Function
See
See
al2n
Alarm 2 Open in Alarm
Alarm 2 must be assigned.
al3n
Alarm 3 Open in Alarm
Alarm 3 must be assigned.
Alarm output operation
Alarm output
Output LCDs
Close in alarm ON
ON
Lit
OFF
OFF
Not lit
Open in alarm ON
OFF
Lit
OFF
ON
Not lit
Setting range
Default
n-o
: Close in alarm,
n-c
: Open in alarm
n-o
Function
Setting
■
Содержание E5AZ
Страница 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Страница 3: ...iv ...
Страница 23: ...xxiv ...
Страница 53: ...30 Using the Support Software Port Section 2 3 ...
Страница 79: ...56 Using HB and HS Alarms Section 3 10 ...
Страница 115: ...92 Output Adjustment Functions Section 4 14 ...
Страница 173: ...150 Communications Setting Level Section 5 8 ...
Страница 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...