147
Advanced Function Setting Level
Section 5-7
• This parameter sets the function to be assigned to alarm output 2.
Note
(1) If
c-o
is assigned for standard control, a value equivalent to 0% will be
output.
(2) If the “standard or heating/cooling” parameter is set to heating/cooling
control when there is E5CZ/CZ-U, control automatically switches to
c-o
.
Related Parameters
Standard or heating/cooling: Page 123, (initial setting level)
alm2
Alarm output 2 Assignment
Alarm output 2 must be assigned.
Setting range
Default
none
: No function is assigned to alarm output 2.
alm2
(See note
2.)
o
:
Heating control output is output.
c-o
:
Cooling control output is output. (See note 1.)
alm1
: Alarm 1 is output.
alm2
: Alarm 2 is output.
alm3
: Alarm 3 is output.
See
See
■