67
Executing Heating/Cooling Control
Section 4-4
Dead Band
• For heating/cooling control, the dead band is set with the set point as its
center. The dead band width is the set value of the “dead band” parame-
ter (adjustment level). Setting a negative value produces an overlapping
band.
• If an overlapping band is set, the bumpless function may not operate
when switching between manual operation and automatic operation.
• The default is 0.0 EU for Controllers with Thermocouple/Resistance Ther-
mometer Universal-inputs and 0.00% FS for Controllers with Analog
Inputs.
Cooling Coefficient
If the heating characteristics and cooling characteristics of the control object
are very different and good control characteristics cannot be achieved with
the same PID constants, the cooling coefficient can be used to adjust the pro-
portional band (P) for the control output assigned to the cooling side. Use this
to achieve balanced control between the heating side and cooling side. The
proportional bands (P) for the control outputs assigned to the heating/cooling
sides can be calculated using the following equations.
P for control output assigned to heating side = P
P for control output assigned to cooling side = P for control output assigned to
heating side
×
cooling coefficient
The cooling coefficient is multiplied by the P for the control output assigned to
the heating side to obtain control with characteristics that differ from those of
the control output assigned to the heating side.
PV
0
PV
0
Output
Dead band: Dead band
width = A positive value
Output
Heating
side
Cooling
side
Set point
Overlapping dead band: Dead
band width = A negative value
Heating
side
Cooling
side
Set point
PV
0
PV
0
Output
Output
P for control output
assigned to heating side
P for control output
assigned to heat-
ing side
×
1.0
P for control output
assigned to cooling side
Set point
P for control output assigned to
heating side
×
0.8
P for control output
assigned to heating side
P for control output
assigned to heat-
ing side
×
1.0
P for control output
assigned to cooling side
P for control output assigned to
heating side
×
1.5
Содержание E5AZ
Страница 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Страница 3: ...iv ...
Страница 23: ...xxiv ...
Страница 53: ...30 Using the Support Software Port Section 2 3 ...
Страница 79: ...56 Using HB and HS Alarms Section 3 10 ...
Страница 115: ...92 Output Adjustment Functions Section 4 14 ...
Страница 173: ...150 Communications Setting Level Section 5 8 ...
Страница 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...