![Omron E5AZ Скачать руководство пользователя страница 180](http://html.mh-extra.com/html/omron/e5az/e5az_user-manual_744338180.webp)
157
Appendix A
Action
Control continues, allowing normal operation. The message is displayed when the PV, PV/SP, or PV/MV is dis-
played.
Meaning
There is an error in internal circuits.
Action
First, turn the power OFF then back ON again. If the display remains the same, the Controller must be
repaired. If the display is restored, then the probable cause is electrical noise affecting the control system.
Check for electrical noise.
Operation at Error
The control outputs and alarm outputs turn OFF. An error message is displayed when the PV, PV/SP, or PV/
MV is displayed.
When the manual MV is set, the control output corresponds to the set value.
For alarm outputs, the operation indicators and status normally turn OFF, but they will turn ON if the “Open in
alarm” parameter for alarms 1, 2, or 3 in the advanced function setting level is set to
n-c
(Open in alarm).
Note
Applies to the E5CZ-
@
2M
@@
with E53-CZH03 or E53-CZHB, E5AZ-
@
3HM
@@,
E5EZ-
@
3HM
@@
.
Meaning
Internal memory operation is in error.
Action
First, turn the power OFF then back ON again. If the display remains the same, the Controller must be
repaired. If the display is restored, then the probable cause is electrical noise affecting the control system.
Check for electrical noise.
Operation at Error
Control output and alarm output turn OFF. (Current output is approx. 0 mA).
−
1999
9999
−
1999
9999
Resistance thermometer input (Except for models with a
setting range of
−
199.9 to 500.0
°
C)
Thermocouple input (Except for models with a setting range of
−
199.9 to 400.0
°
C)
ES1B
Control range
s.err
display
Numeric display
s.err
display
Input indication range
Analog Input
•
When display range < control range
Control range
s.err
display
[[[[
display
Numeric display
Input indication range
]]]]
display
s.err
display
Display range
(See note.)
Resistance thermometer input (Except for models with a
setting range of
−
1999. to 500.0
°
C)
Thermocouple input (Except for models with a setting range of
−
199.9 to 400.0
°
C)
Control range
s.err
display
[[[[
display
Numeric display
Input indication range
s.err
display
Analog Input
•
When display range > control range
Control range
s.err
display
Numeric display
s.err
display
Display range
(See note.)
Note:
The display range is shown in numbers with decimal points omitted.
HB Error (See note.)
h.err
Memory Error
e111
Содержание E5AZ
Страница 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Страница 3: ...iv ...
Страница 23: ...xxiv ...
Страница 53: ...30 Using the Support Software Port Section 2 3 ...
Страница 79: ...56 Using HB and HS Alarms Section 3 10 ...
Страница 115: ...92 Output Adjustment Functions Section 4 14 ...
Страница 173: ...150 Communications Setting Level Section 5 8 ...
Страница 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...