100
Operation Level
Section 5-3
This parameter monitors the set point during SP ramp operation.
A ramp is used to restrict the change width of the set point as a rate of
change.
This parameter is displayed when a set value is input for the “SP ramp set
value” (adjustment level).
When not in ramp operation, the set point will be the same as the one dis-
played for the “process value/set point” parameter.
Related Parameters
Process value/set point (operation level): Page 99
SP ramp set value (adjustment level): Page 116
Set point upper limit, Set point lower limit (initial setting level): Page 122
This parameter measures the heater current from the CT input used for
detecting heater burnout.
This parameter measures and displays the heater current value.
• Heater burnouts are not detected if the control output (heating) ON time is
190 ms or less.
•
ffff
is displayed when 55.0 A is exceeded.
• If a heater burnout is detected, the HA indicator will light, and the relative
setting level will flash on the No. 1 display.
Related Parameters
Heater burnout detection 1 (adjustment level): Page 110
HB ON/OFF (advanced function setting level): Page 135
Error Displays
ct1
: Page 158
sp-m
Set Point During SP Ramp
The “SP ramp set value” parameter
must not be set to OFF.
The “ST” parameter must be set to
OFF.
Monitor range
Unit
SP: SP lower limit to SP upper limit
EU
Function
Monitor
See
See
ct1
Heater Current 1 Value Monitor
Heater burnout and HS alarms must
be supported.
Alarm 1 must be assigned.
The “heater burnout detection”
parameter must be set to ON.
Monitor range
Unit
0.0 to 55.0
A
Function
Monitor
See
See
■
■
Содержание E5AZ
Страница 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Страница 3: ...iv ...
Страница 23: ...xxiv ...
Страница 53: ...30 Using the Support Software Port Section 2 3 ...
Страница 79: ...56 Using HB and HS Alarms Section 3 10 ...
Страница 115: ...92 Output Adjustment Functions Section 4 14 ...
Страница 173: ...150 Communications Setting Level Section 5 8 ...
Страница 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...