![Omron E5AZ Скачать руководство пользователя страница 156](http://html.mh-extra.com/html/omron/e5az/e5az_user-manual_744338156.webp)
133
Advanced Function Setting Level
Section 5-7
Related Parameters
Set point during SP ramp (operation level): Page 100
SP ramp set value (adjustment level): Page 116
• This parameter selects the conditions for enabling reset after the standby
sequence of the alarm has been canceled.
• Output is turned OFF when switching to the initial setting level, communi-
cations setting level, or
advanced function setting level.
• Condition A
Control started (including power ON), and set point, alarm value (alarm
value upper/lower limit), or input shift value (upper/lower-limit temperature
input shift value) changed.
• Condition B
Power ON
• The following example shows the reset action when the alarm type is
lower-limit alarm with standby sequence.
Related Parameters
Alarm 1 to 3 type (initial setting level): Page 124 to 126
Alarm 1 to 3 latch (advanced function setting level): Page 139
Setting range
Default
s
: EU/s,
m
: EU/min
m
See
See
Setting
rest
Standby Sequence Reset
The alarm 1/2/3 type must be set to a
type with a standby sequence.
Setting range
Default
a
: Condition A,
b
: Condition B
a
Function
Alarm
(after change)
Alarm
SP change
Condition A only
Condition A
only
Alarm hysteresis
: Standby sequence canceled
: Standby sequence reset
Alarm output:
Condition A
Alarm output:
Condition B
Setting
See
See
■
■
Содержание E5AZ
Страница 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Страница 3: ...iv ...
Страница 23: ...xxiv ...
Страница 53: ...30 Using the Support Software Port Section 2 3 ...
Страница 79: ...56 Using HB and HS Alarms Section 3 10 ...
Страница 115: ...92 Output Adjustment Functions Section 4 14 ...
Страница 173: ...150 Communications Setting Level Section 5 8 ...
Страница 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...