142
Advanced Function Setting Level
Section 5-7
Alarm 1, 2, or 3 outputs are prevented from turning OFF until after the delay
times set in these parameters have elapsed.
• Set the time for which the OFF delay is to be enabled.
• To disable the OFF delay, set 0.
Related Parameters
Alarm 1 to 3 type (initial setting level): Page 124 to 126
This parameter sets the shift method for thermocouple or resistance ther-
mometer inputs.
• When the input type is thermocouple or resistance thermometer, set
either a 1-point shift or a 2-point shift.
Related Parameters
Temperature input shift: Page 111, Upper-limit temperature input shift value,
Lower-limit temperature input shift value: Page 112 (adjustment level)
Input type (initial setting level): Page 119
a1of
Alarm 1 OFF Delay
Alarm 1 must be assigned, and the
alarm 1 type must not be 0 or 12.
a2of
Alarm 2 OFF Delay
Alarm 2 must be assigned, and the
alarm 2 type must not be 0.
a3of
Alarm 3 OFF Delay
Alarm 3 must be assigned, and the
alarm 3 type must not be 0.
Setting range
Unit
Default
0 to 999
Second
0
Function
Setting
See
See
istp
Input Shift Type
The input type must be thermocou-
ple or resistance thermometer.
Setting range
Default
ins1
: 1-point shift,
ins2
: 2-point shift
ins1
Function
Setting
See
See
■
■
Содержание E5AZ
Страница 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Страница 3: ...iv ...
Страница 23: ...xxiv ...
Страница 53: ...30 Using the Support Software Port Section 2 3 ...
Страница 79: ...56 Using HB and HS Alarms Section 3 10 ...
Страница 115: ...92 Output Adjustment Functions Section 4 14 ...
Страница 173: ...150 Communications Setting Level Section 5 8 ...
Страница 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...