35
Setting the Input Type
Section 3-2
List of Input Types
• The default is 5.
• If a platinum resistance thermometer is mistakenly connected while a set-
ting for other than a platinum resistance thermometer is in effect, S.ERR
will be displayed. To clear the S.ERR display, check the wiring and then
turn the power OFF and back ON.
• The default is 0.
Input type
Specifications
Set value
Input temperature setting range
Controllers
with Ther-
mocouple/
Resistance
Thermome-
ter Univer-
sal-input
Platinum resistance
thermometer
Pt100
0
−
200 to 850 (
°
C)/
−
300 to 1,500 (
°
F)
1
−
199.9 to 500.0 (
°
C)/
−
199.9 to 900.0 (
°
F)
2
0.0 to 100.0 (
°
C)/0.0 to 210.0 (
°
F)
JPt100
3
−
199.9 to 500.0 (
°
C)/
−
199.9 to 900.0 (
°
F)
4
0.0 to 100.0 (
°
C)/0.0 to 210.0 (
°
F)
Thermocouple
K
5
−
200 to 1,300 (
°
C)/
−
300 to 2,300 (
°
F)
6
−
20.0 to 500.0 (
°
C)/0.0 to 900.0 (
°
F)
J
7
−
100 to 850 (
°
C)/
−
100 to 1,500 (
°
F)
8
−
20.0 to 400.0 (
°
C)/0.0 to 750.0 (
°
F)
T
9
−
200 to 400 (
°
C)/
−
300 to 700 (
°
F)
10
−
199.9 to 400.0 (
°
C)/
−
199.9 to 700.0 (
°
F)
E
11
0 to 600 (
°
C)/0 to 1,100 (
°
F)
L
12
−
100 to 850 (
°
C)/
−
100 to 1,500 (
°
F)
U
13
−
200 to 400 (
°
C)/
−
300 to 700 (
°
F)
14
−
199.9 to 400.0 (
°
C)/
−
199.9 to 700.0 (
°
F)
N
15
−
200 to 1,300 (
°
C)/
−
300 to 2,300 (
°
F)
R
16
0 to 1,700 (
°
C)/0 to 3,000 (
°
F)
S
17
0 to 1,700 (
°
C)/0 to 3,000 (
°
F)
B
18
100 to 1,800 (
°
C)/300 to 3,200 (
°
F)
Infrared temperature
sensor ES1B
10 to 70
°
C
19
0 to 90 (
°
C)/0 to 190 (
°
F)
60 to 120
°
C
20
0 to 120 (
°
C)/0 to 240 (
°
F)
115 to 165
°
C
21
0 to 165 (
°
C)/0 to 320 (
°
F)
140 to 260
°
C
22
0 to 260 (
°
C)/0 to 500 (
°
F)
Analog input
0 to 50 mV
23
Either of the following ranges, by scaling:
−
1,999 to 9,999
−
199.9 to 999.9
Input type
Specifications
Set value
Input temperature setting range
Models with
analog
input
Current input
4 to 20 mA
0
Either of the following ranges, by scaling:
−
1,999 to 9,999
−
199.9 to 999.9
−
19.99 to 99.99
−
1.999 to 9.999
0 to 20 mA
1
Voltage input
1 to 5 V
2
0 to 5 V
3
0 to 10 V
4
Содержание E5AZ
Страница 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Страница 3: ...iv ...
Страница 23: ...xxiv ...
Страница 53: ...30 Using the Support Software Port Section 2 3 ...
Страница 79: ...56 Using HB and HS Alarms Section 3 10 ...
Страница 115: ...92 Output Adjustment Functions Section 4 14 ...
Страница 173: ...150 Communications Setting Level Section 5 8 ...
Страница 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...