10
Setting Level Configuration and Key Operations
Section 1-3
1-3
Setting Level Configuration and Key Operations
Parameters are divided into groups, each called a “level.” Each of the set val-
ues (setting items) in these levels is called a “parameter.” The parameters on
the E5CZ/CZ-U/AZ/EZ are divided into the following seven levels.
When the power is turned ON, all of the display lights for approximately 1 sec-
ond.
Note
(1) Operation level entered for software reset.
(2) From the manual control level, key operations can be used to move to the
operation level only.
Of these levels, the initial setting level, communications setting level,
and advanced function setting level can be used only when control is
stopped. Control outputs are stopped when any of these three levels
is selected.
(See
note
3.)
(See
note 1.)
Power ON
Started in manual mode.
Manual
mode
Press the
O
Key
for at least 1 s.
Press the
O
Key
for at least 1 s;
display will flash.
Press the
O
Key
for at least 3 s while
a-m
is displayed.
Manual Control
Level
Operation Level
Press the
O
Key for
at least 1 s.
Initial Setting Level
Press the
O
Key
for at least 1 s.
Advanced Function
Setting Level
Input password.
Set value
−
169
Press the
O
Key less than 1 s.
Communica-
tions Setting
Level
Press the
O
Key for at
least 1 s; display will flash.
Press the
O
Key for at
least 3 s.
Control stops.
Press the
O
Key for less than 1 s.
Adjustment Level
Press the
O
+
M
Keys for at
least 1 s.
Press the
O
+
M
keys; display
will flash.
Press the
O
+
M
Keys for at
least 3 s. (See
note.)
Protect level
Note:
The time taken to move
to the protect level can
be adjusted by
changing the "Move to
protect level time"
setting.
Control in progress
Level change
Not displayed for some models
Control stopped
Started in automatic mode.
a-m
C
25
100
C
25
100
C
Level
Control in progress
Control stopped
Protect level
Can be set.
---
Operation level
Can be set.
---
Adjustment level
Can be set.
---
Manual control level
Can be set.
---
Initial setting level
---
Can be set.
Advanced function setting level
---
Can be set.
Communications setting level
---
Can be set.
Содержание E5AZ
Страница 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Страница 3: ...iv ...
Страница 23: ...xxiv ...
Страница 53: ...30 Using the Support Software Port Section 2 3 ...
Страница 79: ...56 Using HB and HS Alarms Section 3 10 ...
Страница 115: ...92 Output Adjustment Functions Section 4 14 ...
Страница 173: ...150 Communications Setting Level Section 5 8 ...
Страница 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...