116
Adjustment Level
Section 5-4
• This parameter sets the rate of change during SP ramp operation. Set the
maximum permissible change width per unit of time as the SP ramp set
value. The SP ramp function is disabled if this parameter is set to OFF.
• During temperature input, the decimal point position of the SP ramp set
value is dependent on the currently selected sensor, and during analog
input it is dependent on scaling.
Related Parameters
Input type: Page 119, Scaling upper limit, Scaling lower limit, Decimal point
(initial setting level): Page 121, ST: Page 123 (initial setting level)
SP ramp time unit (advanced function setting level): Page 132
• The “MV upper limit” and “MV lower limit” parameters set the upper and
lower limits of the manipulated variable. When the calculated manipulated
variable exceeds the upper or lower limit value, the upper or lower limit
value will be the output level.
• MV Upper Limit
The setting ranges during standard control and heating/cooling control
are different.
The manipulated variable for the cooling control output side during heat-
ing/cooling control is expressed as a negative value.
• MV Lower Limit
The setting ranges during standard control and heating/cooling control
are different. The manipulated variable for the cooling control output side
during heating/cooling control is expressed as a negative value.
Related Parameters
PID ON/OFF: Page 122, ST: Page 123 (initial setting level)
sprt
SP Ramp Set Value
The “ST” parameter must be set to
OFF.
Setting range
Unit
Default
OFF or 1 to 9999
EU/s or EU/minute
off
Function
Setting
See
See
ol-h
MV Upper Limit
The control must be set to 2-PID
control.
The “ST” parameter must be set to
OFF.
ol-l
MV Lower Limit
Control method
Setting range
Unit
Default
Standard
MV lower limit + 0.1 to 105.0
%
105.0
Heating/cooling
0.0 to 105.0
Control method
Setting range
Unit
Default
Standard
−
5.0 to MV upper limit
−
0.1
%
−
5.0
Heating/cooling
−
105.0 to 0.0
−
105.0
Function
Setting
See
See
■
■
Содержание E5AZ
Страница 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Страница 3: ...iv ...
Страница 23: ...xxiv ...
Страница 53: ...30 Using the Support Software Port Section 2 3 ...
Страница 79: ...56 Using HB and HS Alarms Section 3 10 ...
Страница 115: ...92 Output Adjustment Functions Section 4 14 ...
Страница 173: ...150 Communications Setting Level Section 5 8 ...
Страница 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...