53
Using HB and HS Alarms
Section 3-10
3-10-5 Settings (HB alarm)
To activate the heater burnout alarm, set the “heater burnout detection”
parameter to ON in the advanced function setting level and set the “heater
burnout detection 1” parameter in the adjustment level.
Operating Procedure
This procedure sets the “heater burnout detection 1” parameter to 2.5.
Moving to the Advanced Function Setting Level
The “heater burnout detection” parameter setting is already ON by default, so
set the “heater burnout detection 1” parameter.
Setting Heater Burnout Detection
Operation Level
1.
Move to the advanced function setting level.
Press the
O
key for at least three seconds to move from the operation
level to the initial setting level.
Initial Setting Level
2.
Select “move to advanced function setting level” by pressing the
M
key.
Initial Setting Level
3.
Press the
D
key to enter the password (
−
169), and move from the initial
setting level to the advanced function setting level.
Advanced Function Setting Level
The top parameter in the advanced function setting level is displayed.
4.
Select the “heater burnout detection” parameter by pressing the
M
key.
Check that this parameter is set to ON (the default).
Next, set the “heater current 1 value monitor” parameter.
Operation Level
5.
Press the
O
key for at least one second to move from the advanced func-
tion setting level to the initial setting level and then to the operation level.
Adjustment Level
6.
Press the
O
key for less than one second to move from the operation lev-
el to the adjustment level.
7.
Select the “heater current 1 value monitor” parameter by pressing the
M
key. Check the current value. Next, set the “heater burnout detection 1”
parameter.
8.
Select the “heater burnout detection 1” parameter by pressing the
M
key.
Refer to
3-10-3 Calculating Detection Current Values
on page 51 when
making the settings.
C
25
100
PV/SP
in-t
5
Input type
amov
-169
Moves to ad-
vanced function
setting level
init
off
hbu
on
Heater burnout
detection
C
25
100
PV/SP
at
off
AT execute/
cancel
ct1
0.0
Heater current
1 value monitor
hb1
0.0
Heater burnout
detection 1
■
■
Содержание E5AZ
Страница 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Страница 3: ...iv ...
Страница 23: ...xxiv ...
Страница 53: ...30 Using the Support Software Port Section 2 3 ...
Страница 79: ...56 Using HB and HS Alarms Section 3 10 ...
Страница 115: ...92 Output Adjustment Functions Section 4 14 ...
Страница 173: ...150 Communications Setting Level Section 5 8 ...
Страница 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...