87
Performing Manual Control
Section 4-12
Operating Procedure
Use the following procedure to set the manipulated variable in manual mode.
Operation Level
Initial Setting Level
1.
Press the
O
key for at least three seconds to move from the operation
level to the initial setting level.
2.
Select the “PID ON/OFF” parameter by pressing the
M
key.
Initial Setting Level
3.
Select the “move to advanced function setting level” parameter by press-
ing the
M
key.
Advanced Function Setting Level
4.
Press the
D
key to enter the password (
−
169), and move from the initial
setting level to the advanced function setting level.
Advanced Function Setting Level
5.
Select the “auto/manual select addition” parameter by pressing the
M
key.
6.
Use the
U
key to set the parameter to ON.
Initial Setting Level
7.
Press the
O
key for at least one second to move from the advanced func-
tion setting level to the initial setting level.
8.
Press the
O
key for at least one second to move from the initial setting
level to the operation level.
Operation Level
9.
Select the “auto/manual switch” parameter by pressing the
M
key.
Manual Control Level
10. Press the
O
key for at least three seconds to move from the operation
level to the manual control level.
C
25
100
PV/SP
in-t
5
Input type
cntl
pid
amov
0
Move to ad-
vanced function
setting level
init
off
Parameter
initialization
amad
off
Auto/manual
select addition
amad
on
in-t
5
Input type
a-m
Auto/manual
switch
C
25
0.0
PV/MV
Содержание E5AZ
Страница 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Страница 3: ...iv ...
Страница 23: ...xxiv ...
Страница 53: ...30 Using the Support Software Port Section 2 3 ...
Страница 79: ...56 Using HB and HS Alarms Section 3 10 ...
Страница 115: ...92 Output Adjustment Functions Section 4 14 ...
Страница 173: ...150 Communications Setting Level Section 5 8 ...
Страница 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...