144
Advanced Function Setting Level
Section 5-7
• This parameter sets the hysteresis for HS alarm.
Related Parameter
HS alarm use (advanced function setting level): Page 143
This parameter enables or disables the LBA function and sets the detection
time interval.
• Set the time interval for detecting loop burnouts.
• To disable the LBA function, set 0.
Related Parameters
Alarm 1 type (initial setting level): Page 124
LBA level, LBA band: Page 145 (advanced function setting level)
hsh
HS Alarm Hysteresis
Heater burnout and HS alarms must
be supported.
Alarm 1 must be assigned.
The “HS alarm” parameter must be
set to ON.
The “HS alarm latch” must be set to
OFF.
Setting range
Unit
Default
0.1 to 50.0
A
0.1
Function
Setting
See
See
lba
LBA Detection Time
Alarm 1 must be assigned.
The alarm type must be set to 12
(LBA).
Setting range
Unit
Default
0 to 9999
Second
0
Function
Setting
See
See
■
■