xiv
1)
It takes approximately 2 seconds for the outputs to turn ON from after the power supply is turned ON. Due
consideration must be given to this time when incorporating Temperature Controllers into a control panel
or similar device.
2)
Make sure that the Temperature Controller has 30 minutes or more to warm up after turning ON the
power before starting actual control operations to ensure the correct temperature display.
3)
When executing self-tuning, turn ON power for the load (e.g., heater) at the same time as or before
supplying power to the Temperature Controller. If power is turned ON for the Temperature Controller
before turning ON power for the load, self-tuning will not be performed properly and optimum control will
not be achieved. When starting operation after the Temperature Controller has warmed up, turn OFF the
power and then turn it ON again at the same time as turning ON power for the load. (Instead of turning the
Temperature Controller OFF and ON again, switching from STOP mode to RUN mode can also be used.)
4)
Avoid using the Controller in places near a radio, television set, or wireless installing. The Controller may
cause radio disturbance for these devices.
Be sure to thoroughly read and understand the manual provided with the product, and check the fol-
lowing points.
Note
The tightening torque for E5CZ-U is 0.5 N·m.
Precautions for Operation
Preparations for Use
Timing
Check point
Details
Purchasing the prod-
uct
Product appearance
After purchase, check that the product and packaging are not dented or
otherwise damaged. Damaged internal parts may prevent optimum
control.
Product model and speci-
fications
Make sure that the purchased product meets the required specifica-
tions.
Setting the Unit
Product installation loca-
tion
Provide sufficient space around the product for heat dissipation. Do not
block the vents on the product.
Wiring
Terminal wiring
Do not subject the terminal screws to excessive stress (force) when
tightening them.
Make sure that there are no loose screws after tightening terminal
screws to the specified torque of 0.74 to 0.90 N·m.(See note.)
Be sure to confirm the polarity for each terminal before wiring the termi-
nal block and connectors.
Power supply inputs
Wire the power supply inputs correctly. Incorrect wiring will result in
damage to the internal circuits.
Operating environ-
ment
Ambient temperature
The ambient operating temperature for the product is
−
10 to 55
°
C (with
no condensation or icing). To extend the service life of the product,
install it in a location with an ambient temperature as low as possible. In
locations exposed to high temperatures, if necessary, cool the products
using a fan or other cooling method.
Vibration and shock
Check whether the standards related to shock and vibration are satis-
fied at the installation environment. (Install the product in locations
where the conductors will not be subject to vibration or shock.)
Foreign particles
Install the product in a location that is not subject to liquid or foreign
particles entering the product.
Содержание E5AZ
Страница 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Страница 3: ...iv ...
Страница 23: ...xxiv ...
Страница 53: ...30 Using the Support Software Port Section 2 3 ...
Страница 79: ...56 Using HB and HS Alarms Section 3 10 ...
Страница 115: ...92 Output Adjustment Functions Section 4 14 ...
Страница 173: ...150 Communications Setting Level Section 5 8 ...
Страница 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...