Setting Output Specifications
Section 3-5
3-5-2
Direct and Reverse Operation
• “Direct operation” increases the manipulated variable whenever the pro-
cess value increases. “Reverse operation” decreases the manipulated
variable whenever the process value increases.
For example, when the process value (PV) is lower than the set point (SP)
in a heating control system, the manipulated variable increases according
to the difference between the PV and SP. Accordingly, reverse operation
is used in a heating control system. Direct operation is used in a cooling
control system, in which the operation is the opposite of a heating control
system.
• Direct/reverse operation is set in the “direct/reverse operation” parameter
in the initial setting level. The default is
or-r
(reverse operation).
Operating Procedure
In this example, the input type, temperature unit, direct/reverse operation, and
control period (heating) parameters are checked.
Input type =
s
(K thermocouple)
Temperature unit =
c
(
°
C)
Direct/reverse operation =
or-r
(reverse operation)
Control period (heating) = 20 (seconds)
orev
100%
0%
100%
0%
Manipulated variable
Manipulated variable
Low
temperature
Set Value
High
temperature
Low
temperature
Set Value
High
temperature
Direct operation
Reverse operation
Operation Level
1.
Press the
O
key for at least three seconds to move from the operation
level to the initial setting level.
Initial Setting Level
2.
The input type is displayed. When the input type is being set for the first
time,
s
(K thermocouple) is set. To select a different sensor, press the
U
or
D
key.
3.
Select the “temperature unit” parameter by pressing the
M
key. The de-
fault is
c
(
°
C). To select
f
(
°
F), press the
U
key.
4.
Select the “control period (heating)” parameter by pressing the
M
key.
The default is 20.
C
30
0
in-t
5
Input type
d-u
c
Temperature unit
cp
20
Control period
(heating)
Содержание E5AZ
Страница 2: ...E5CZ E5CZ U E5AZ E5EZ Digital Temperature Controller User s Manual Produced September 2008 ...
Страница 3: ...iv ...
Страница 23: ...xxiv ...
Страница 53: ...30 Using the Support Software Port Section 2 3 ...
Страница 79: ...56 Using HB and HS Alarms Section 3 10 ...
Страница 115: ...92 Output Adjustment Functions Section 4 14 ...
Страница 173: ...150 Communications Setting Level Section 5 8 ...
Страница 205: ...182 Index precautions 22 terminal arrangement 21 terminals 21 ...