25: Unit error
02
Parity/checksum error occurred
because of incorrect data.
Transfer correct data into memory.
03
I/O setting error (The registered I/O
configuration differs from the actual.)
Either change the actual configuration to
match the registered one, or generate the I/
O table again.
04
Too many I/O points
Redesign the system to remain within per-
missible limits.
05
CPU bus error (An error occurred dur-
ing data transfer between the CPU and
a CPU Bus Unit.)
Check the unit and cable connections and
issue the ERROR CLEAR command.
06
I/O duplication error (A rack number,
unit number, or I/O word allocation has
been duplicated.)
Check the system’s settings and eliminate
any duplication.
07
I/O bus error (An error occurred during
data transfer between the CPU and an
I/O Unit.)
Check the unit and cable connections and
issue the ERROR CLEAR command.
09
SYSMAC BUS/2 error (An error
occurred during SYSMAC BUS/2 data
transfer.)
Check the unit and cable connections and
issue the ERROR CLEAR command.
0A
Special I/O Unit error (An error
occurred during CPU Bus Unit data
transfer.)
Check the unit and cable connections and
issue the ERROR CLEAR command.
0D
Duplication in SYSMAC BUS word allo-
cation.
Check and regenerate the I/O table.
0F
A memory error has occurred in inter-
nal memory, in the Memory Card, or in
Expansion DM during the error check.
If the error occurred in internal memory or
the EM Unit, correct the data in the com-
mand an execute it again.
If the error occurred in a Memory Card or
EM used for file memory, the file data has
been corrupted. Execute the MEMORY
CARD FORMAT command.
If the above remedies do not eliminate the
error, replace the faulty memory.
10
Terminator not connected in SYSMAC
BUS System.
Connect the terminator correctly.
Main code
Sub-
code
Probable cause
Remedy
Содержание CS1W-SLK11-21 - 06-2004
Страница 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Страница 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ......
Страница 11: ......
Страница 17: ......
Страница 49: ......
Страница 107: ......
Страница 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Страница 143: ......
Страница 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Страница 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Страница 177: ......
Страница 179: ......
Страница 195: ......
Страница 199: ......
Страница 201: ...Authorized Distributor Cat No W367 E1 02 Note Specifications subject to change without notice Printed in Japan...
Страница 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...