29
Cable Connections
Section 2-4
• To prevent the Optical Fiber Cable from being pulled too forcefully, always
use the cable securing bracket and provide space behind the Unit as
shown in the following diagram. Do not exceed the maximum tension for
the cord and cable:
Cord:
0 kg (Do not apply any tension.)
Cable: 5 kg
• Do not place objects on top of the Optical Fiber Cable. The maximum
pressure that can be placed on the cord and cable is as follows:
Cord:
30 kg/10 cm
Cable: 50 kg/10 cm
• Inspect the connector before installing it.
Connection Procedure
Use the following procedure to connect Optical Fiber Cables to a Unit.
1,2,3...
1.
Tighten screws in the mounting brackets so that the through-holes on the
terminal are on the top and bottom and then affix hexagonal nuts from the
opposite side of the terminal.
2.
Insert bushing to the mounting bracket and secure the Unit with screws.
3.
Pass the tension member through the through-holes, and tighten the ter-
minal screws to affix the tension member.
4.
Affix the cable to the mounting bracket so that it is clamped by the bracket.
Two cables can be attached at the same time.
5.
Move the cable connector so that the loose ends are on the left-hand side,
and insert the Unit’s optical connector as far as it will reach.
2-4-3
Backup Power Supply
Each node requires a backup power supply for the node bypass function. Sev-
eral nodes can be connected to a single power supply or each node can be
connected to an independent power supply.
Be sure that the backup power supply is providing sufficient current and volt-
age at the Unit’s connector.
Backup Power Supply
Specifications
The following table shows the input specifications required for backup power
supply to SYSMAC LINK Units. Be sure that the backup power supply being
used meets these specifications. (We recommend the OMRON S82K-series
Power Supplies.)
50
60
200
Cord
Cable
Item
Specification
Voltage
24 V DC
Allowed voltage fluctuation
20.4 to 26.4 V DC (24 V DC –15% to +10%)
Содержание CS1W-SLK11-21 - 06-2004
Страница 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Страница 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ......
Страница 11: ......
Страница 17: ......
Страница 49: ......
Страница 107: ......
Страница 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Страница 143: ......
Страница 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Страница 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Страница 177: ......
Страница 179: ......
Страница 195: ......
Страница 199: ......
Страница 201: ...Authorized Distributor Cat No W367 E1 02 Note Specifications subject to change without notice Printed in Japan...
Страница 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...