110
FINS Command/Response Format
Section 6-3
6-3-4
FINS Commands for PLCs
Note
When the PLC is in RUN mode, data transfers from files to the program area
are not possible, but transfers from the program area to files are possible.
Command
code
Name
PLC mode
RUN
MONITOR
DEBUG
PROGRAM
01
01
MEMORY AREA READ
Valid
Valid
Valid
Valid
02
MEMORY AREA WRITE
Valid
Valid
Valid
Valid
03
MEMORY AREA FILL
Valid
Valid
Valid
Valid
04
MULTIPLE MEMORY AREA READ
Valid
Valid
Valid
Valid
05
MEMORY AREA TRANSFER
Valid
Valid
Valid
Valid
02
01
PARAMETER AREA READ
Valid
Valid
Valid
Valid
02
PARAMETER AREA WRITE
Valid
Valid
Valid
Valid
03
PARAMETER AREA CLEAR
Valid
Valid
Valid
Valid
03
04
PROGRAM AREA PROTECT
Valid
Valid
Valid
Valid
05
PROGRAM AREA PROTECT CLEAR
Valid
Valid
Valid
Valid
06
PROGRAM AREA READ
Valid
Valid
Valid
Valid
07
PROGRAM AREA WRITE
Not valid
Valid
Valid
Valid
08
PROGRAM AREA CLEAR
Not valid
Not valid
Not valid
Valid
04
01
RUN
Valid
Valid
Valid
Valid
02
STOP
Valid
Valid
Valid
Valid
05
01
CONTROLLER DATA READ
Valid
Valid
Valid
Valid
02
CONNECTION DATA READ
Valid
Valid
Valid
Valid
06
01
CONTROLLER STATUS READ
Valid
Valid
Valid
Valid
20
CYCLE TIME READ
Valid
Valid
Not valid
Not valid
07
01
CLOCK READ
Valid
Valid
Valid
Valid
02
CLOCK WRITE
Valid
Valid
Valid
Valid
09
20
MESSAGE READ
Valid
Valid
Valid
Valid
MESSAGE CLEAR
Valid
Valid
Valid
Valid
FAL/FALS READ
Valid
Valid
Valid
Valid
0C
01
ACCESS RIGHT ACQUIRE
Valid
Valid
Valid
Valid
02
ACCESS RIGHT FORCED ACQUIRE
Valid
Valid
Valid
Valid
03
ACCESS RIGHT RELEASE
Valid
Valid
Valid
Valid
21
01
ERROR CLEAR
Valid
Valid
Valid
Valid
02
ERROR LOG READ
Valid
Valid
Valid
Valid
03
ERROR LOG CLEAR
Valid
Valid
Valid
Valid
22
01
FILE NAME READ
Valid
Valid
Valid
Valid
02
SINGLE FILE READ
Valid
Valid
Valid
Valid
03
SINGLE FILE WRITE
Valid
Valid
Valid
Valid
04
MEMORY CARD FORMAT
Valid
Valid
Valid
Valid
05
FILE DELETE
Valid
Valid
Valid
Valid
06
VOLUME LABEL CREATE/DELETE
Valid
Valid
Valid
Valid
07
FILE COPY
Valid
Valid
Valid
Valid
08
FILE NAME CHANGE
Valid
Valid
Valid
Valid
09
FILE DATA CHECK
Valid
Valid
Valid
Valid
0A
MEMORY AREA FILE TRANSFER
Valid
Valid
Valid
Valid
0B
PARAMETER AREA FILE TRANSFER
Valid
Valid
Valid
Valid
0C
PROGRAM AREA FILE TRANSFER
(see note)
Valid
Valid
Valid
23
01
FORCED SET/RESET
Not valid
Valid
Valid
Valid
02
FORCED SET/RESET CANCEL
Not valid
Valid
Valid
Valid
Содержание CS1W-SLK11-21 - 06-2004
Страница 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Страница 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ......
Страница 11: ......
Страница 17: ......
Страница 49: ......
Страница 107: ......
Страница 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Страница 143: ......
Страница 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Страница 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Страница 177: ......
Страница 179: ......
Страница 195: ......
Страница 199: ......
Страница 201: ...Authorized Distributor Cat No W367 E1 02 Note Specifications subject to change without notice Printed in Japan...
Страница 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...