![background image](http://html1.mh-extra.com/html/omron/cs1w-slk11-21-06-2004/cs1w-slk11-21-06-2004_manual_743560090.webp)
73
CX-Programmer Procedures
Section 4-12
6.
Set the settings for node 2 and 3 in the same way. The following example
shows the settings for node 2.
The following example shows the settings for node 3.
Node address
Local node address: 1
Common link
parameters
CIO Area size CIO Area local node send size: 20 words.
DM Area size DM Area local node send size: 30 words.
Refresh
parameters
PLC type
Select “CV/CVM1”
Start
word
CIO
CIO Area local node data link start address:
CIO 1000.
DM
DM Area local node data link start address: D00500
Refresh
nodes
Node refresh order: 1, 3, 2
Node addresses are listed in order with the starting
node address first. Because here the local node is
listed first, node 1 will first send data and then
received data in order from nodes 3 and then 2.
Содержание CS1W-SLK11-21 - 06-2004
Страница 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Страница 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ......
Страница 11: ......
Страница 17: ......
Страница 49: ......
Страница 107: ......
Страница 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Страница 143: ......
Страница 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Страница 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Страница 177: ......
Страница 179: ......
Страница 195: ......
Страница 199: ......
Страница 201: ...Authorized Distributor Cat No W367 E1 02 Note Specifications subject to change without notice Printed in Japan...
Страница 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...