99
PLC Network Instructions
Section 6-2
6-2-6
NETWORK RECEIVE Instruction - RECV(98)
The RECV(98) instruction enables the local node to write to its memory, data
sent from a node either on a local or remote network.
Format
The format of the RECV(98) instruction is as follows:
Control Data
Set the source node address to $00 to send data within the PLC executing the
instruction.
Note
Transmissions cannot be received from the PLC executing RECV(98).
1,2,3...
1.
Number of Words
Set the total number of words to be transferred.
2.
Source Network Address
Set the Source network address to 00 if you send the data to within the lo-
cal network. If more than one SYSMAC LINK Unit, Controller Link Unit, or
Ethernet Unit is mounted on the PLC, the network of the Unit with the
smallest unit address will be considered to the local network.
3.
Source Node Address
Set the source node address to 00 for devices at the local node.
4.
Source Unit Address
Set the source unit address to 00 if the destination is a PLC. If it is a user
application on a computer, set the destination unit to 01 (user application
01). For a BASIC Unit, add 10 to the unit number (0 to F) so that the des-
tination unit address is from 10 to 1F.
5.
Response Bit (Bit 15 of C+3)
Always set this bit to OFF (0: response required).
Variations
@RECV(98)
(98)
RECV
S
D
C
D: 1
st
destination word
CIO, W, H, A, T, C, DM, DR*, IR*
C: 1
st
control word
CIO, W, H, A, T, C, DM, DR*, IR*
*Indirect addressing only
S: 1
st
source word
CIO, W, H, A, T, C, DM, DR*, IR*
Operand Data Areas
Ladder Symbol
Word
Bits 00 to 07
Bits 08 to 15
C
Number of words (1 to 256 in 4-digit hexadecimal, i.e., $0001 to $0100)
C+1
Source network address
(0 to 127, i.e., $00 to $7F)
Bits 08 to 15: Set to 0.
C+2
Source unit address
Source node address
C+3
Bits 00 to 03: No. of retries
(0 to 15 Hex, i.e., $0 to $F)
Bits 04 to 07: Set to 0.
Bits 08 to 11: Port number ($0 to $7)
Bit 12 to 14: Set to 0.
Bit 15: ON: No response.
OFF: Response returned.
C+4
Response monitoring time ($0001 to $FFFF = 0.1 to 6553.5 seconds)
Destination
Address (hexadecimal)
PLC (CPU)
00
NSB (computer)
01 (user application)
CPU Bus Unit
10 to 1F: Unit Number 0 to F (0 to15)
Inner Board
E1
Unit connected with the network
FE
Содержание CS1W-SLK11-21 - 06-2004
Страница 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Страница 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ......
Страница 11: ......
Страница 17: ......
Страница 49: ......
Страница 107: ......
Страница 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Страница 143: ......
Страница 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Страница 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Страница 177: ......
Страница 179: ......
Страница 195: ......
Страница 199: ......
Страница 201: ...Authorized Distributor Cat No W367 E1 02 Note Specifications subject to change without notice Printed in Japan...
Страница 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...