135
Troubleshooting
Section 8-1
Network Relay Errors
For network relay errors using SEND(90) or RECV(98), check the path of the
command using the routing tables and the nature of the error using the
response code to eliminate the cause of the error.
For network relay errors using CMND(490), the location of the relay error is
recorded in the second and third words of the response, as shown below.
Network error address: 00 to 7F (0 to 127)
Node error address
SYSMAC LINK: 01 to 3E (1 to 62)
Controller Link: 01 to 20 (1 to 32)
26: Command error
01
The specified area is not protected.
This response code will be returned if
an attempt is made to clear protection
on an area that is not protected.
The program area is not protected, so it is
not necessary to clear protection.
02
An incorrect password has been speci-
fied.
Specify a password that is registered.
04
The specified area is protected.
Execute the command again after the PRO-
GRAM AREA PROTECT CLEAR com-
mand.
05
The service is being executed.
Execute the command again after the ser-
vice has been completed or aborted.
06
The service is not being executed.
Execute the service if necessary.
07
Service cannot be executed from local
node because the local node is not part
of the data link.
Execute the service from a node that is part
of the data link.
08
The communications cycle time in the
data link table is too short. (The LNK
indicator will be flashing rapidly.)
Either use the automatic setting or increase
the setting manually.
09
Service cannot be executed because
the necessary settings have not been
made in the command data.
Check the command format and make the
necessary settings.
0A
The specified action or transition num-
ber has already been registered.
Execute the command again using an
action or transition number that has not
been registered.
0B
Cannot clear error because the cause
of the error still exists.
Eliminate the cause of the error and exe-
cute the ERROR CLEAR command.
30: Access right error
01
The access right is held by another
device.
Execute the command again after the
access right has been released.
(The command can be executed after the
ACCESS RIGHT FORCED ACQUIRE or
ACCESS RIGHT RELEASE command is
completed. Releasing the access right
might affect processes in progress at the
node that held the access right.)
Main code
Sub-
code
Probable cause
Remedy
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Main response code
Sub response code
Bit
1: Nonfatal CPU Unit Error Flag
1: Fatal CPU Unit Error Flag
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Error network address
Error node address
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
0
0
Bit
First word
Second word
Third word
Command code
1: Relay Error Flag
Содержание CS1W-SLK11-21 - 06-2004
Страница 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Страница 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ......
Страница 11: ......
Страница 17: ......
Страница 49: ......
Страница 107: ......
Страница 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Страница 143: ......
Страница 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Страница 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Страница 177: ......
Страница 179: ......
Страница 195: ......
Страница 199: ......
Страница 201: ...Authorized Distributor Cat No W367 E1 02 Note Specifications subject to change without notice Printed in Japan...
Страница 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...