59
Data Link Status
Section 4-9
4-9-2
Word Structure
The following table shows the data link status in memory. The numbers within
the table are in order of the nodes are set in the data link table (refresh param-
eters). These will correspond to the node addresses when using automatic
settings.
The data link status area corresponds to the first word of the words allocated
to the SYSMAC LINK Unit as a CPU Bus Unit +8 to +23.
Word: CIO 1500 + (25 x unit number) +8 to +23.
The status of the bits allocated to each node is as follows:
Bit 00, 04, 08, or 12:
CPU Unit Operating Flag
Bit 01, 05, 09, or 13:
CPU Unit Error Flag
Bit 02, 06, 10, or 14:
Data Link Communications Error Flag
Bit 03, 07, 11, or 15:
Data Link Active Flag
The actual words allocated to each node address for data link status are
shown in the following table.
If the Local Node Data Link Active Flag (bit 15 of first word +23) is OFF, the
data link status will be maintained as it was immediately before operation
stopped. This may not be the same as the actual current status. When using
Word
Bits 00 to 03
Bits 04 to 07
Bits 08 to 11
Bits 12 to 15
m+8
Link No. 1
Link No. 2
Link No. 3
Link No. 4
m+9
Link No. 5
Link No. 6
Link No. 7
Link No. 8
m+10
Link No. 9
Link No. 10
Link No. 11
Link No. 12
m+11
Link No. 13
Link No. 14
Link No. 15
Link No. 16
m+12
Link No. 17
Link No. 18
Link No. 19
Link No. 20
m+13
Link No. 21
Link No. 22
Link No. 23
Link No. 24
m+14
Link No. 25
Link No. 26
Link No. 27
Link No. 28
m+15
Link No. 29
Link No. 30
Link No. 31
Link No. 32
m+16
Link No. 33
Link No. 34
Link No. 35
Link No. 36
m+17
Link No. 37
Link No. 38
Link No. 39
Link No. 40
m+18
Link No. 41
Link No. 42
Link No. 43
Link No. 44
m+19
Link No. 45
Link No. 46
Link No. 47
Link No. 48
m+20
Link No. 49
Link No. 50
Link No. 51
Link No. 52
m+21
Link No. 53
Link No. 54
Link No. 55
Link No. 56
m+22
Link No. 57
Link No. 58
Link No. 59
Link No. 60
m+23
Link No. 61
Link No. 62
Bits 08 to 13: Address of startup
node (01 to 3E Hex)
Bit 15: Local Data Link Active
Flag (ON: data link active;
OFF: data link inactive)
Unit No.
Words
Unit No.
Words
0
CIO 1508 to CIO 1523
8
CIO 1708 to CIO 1723
1
CIO 1533 to CIO 1548
9
CIO 1733 to CIO 1748
2
CIO 1558 to CIO 1573
10
CIO 1758 to CIO 1773
3
CIO 1583 to CIO 1598
11
CIO 1783 to CIO 1798
4
CIO 1608 to CIO 1623
12
CIO 1808 to CIO 1823
5
CIO 1633 to CIO 1648
13
CIO 1833 to CIO 1848
6
CIO 1658 to CIO 1673
14
CIO 1858 to CIO 1873
7
CIO 1683 to CIO 1698
15
CIO 1883 to CIO 1898
Содержание CS1W-SLK11-21 - 06-2004
Страница 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Страница 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ......
Страница 11: ......
Страница 17: ......
Страница 49: ......
Страница 107: ......
Страница 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Страница 143: ......
Страница 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Страница 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Страница 177: ......
Страница 179: ......
Страница 195: ......
Страница 199: ......
Страница 201: ...Authorized Distributor Cat No W367 E1 02 Note Specifications subject to change without notice Printed in Japan...
Страница 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...