PLC Network Instructions
Section 6-2
(3) When executing the SEND(90) or RECV(98) instruction on memory in the
LR Area, HR Area, or AR Area between a CS-series, CVM1, or CV-series
PLC and a C-series PLC (C200HX/HG/HE/HS/H, C1000H, or C2000H),
instead of the LR Area, HR Area, or AR Area addresses, use the corre-
sponding addresses given in the following table.
(4) It is not possible to specify the CPU Bus Link Area in a CVM1 or CV-se-
ries PLC from a CS-series PLC.
(5) It is not possible to specify the Work Area or Holding Area in a CS-series
PLC from a CVM1, CV-series, or C-series PLC.
(6) When executing the SEND(90) or RECV(490) instruction on a CS-series
PLC from a CVM1 or CV-series PLC, the areas that can be specified are
restricted to the areas of memory built into the CVM1 or CV-series PLC.
The SEND(90) and RECV(490) instructions cannot be executed on mem-
ory outside these areas.
(7) When executing the SEND(90) or RECV(98) instruction on a CS-series,
CVM1, or CV-series PLC from a C-series PLC, the areas that can be
specified are restricted to the areas of memory built into the C-series PLC
from which the instruction is executed. The SEND(90) and RECV(490) in-
structions cannot be executed on memory outside these areas. For de-
tails on C-series PLC memory areas, refer to the relevant operation
manual. When using a C200HW-SLK13/14/23/24 with a C200HX/HG/HE
mounted to it, however, the SEND(90) or RECV(490) instructions can be
executed for all areas except for the Work Area and Holding Area in CS-
series PLCs and the CPU Bus Line Area in CVM1 or CV-series PLCs by
using indirect addressing. Refer to the
C-series SYSMAC LINK System
Manual
(W174) for details.
(8) Specification of indirect DM Area from a C-series PLC corresponds to the
EM Area’s current bank. Use indirect addressing to access a specified
bank number of the EM Area from a C-series PLC.
6-2-4
Communications Ports
When the SEND(90), RECV(98), or CMND(490) instructions have been exe-
cuted, the status of the execution will be stored in the Auxiliary Area of the
PLC according to the communications port. Using this status information, the
PLC can adjust the timing of SEND(90), RECV(98), or CMND(490) execution
from the user’s program.
Timing Communications
Ports
Eight communications ports can be used simultaneously to execute the
SEND(90), RECV(98), or CMND(490) instructions, but only one instruction
Area in C-series PLC
Corresponding area in CS-series,
CVM1, or CV-series PLC
LR00 to LR63
1000 to 1063
HR00 to HR99
1064 to 1163
AR00 to AR27
1164 to 1191
Specified area in CVM1 or CV-series
PLC
Settable range
CIO
0000 to 2555
AR
A000 to A511
TIM
T0000 to T1023
CNT
C0000 to C1023
DM
D00000 to D24575
EM
E00000 to E32765
Содержание CS1W-SLK11-21 - 06-2004
Страница 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Страница 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ......
Страница 11: ......
Страница 17: ......
Страница 49: ......
Страница 107: ......
Страница 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Страница 143: ......
Страница 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Страница 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Страница 177: ......
Страница 179: ......
Страница 195: ......
Страница 199: ......
Страница 201: ...Authorized Distributor Cat No W367 E1 02 Note Specifications subject to change without notice Printed in Japan...
Страница 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...