30
Cable Connections
Section 2-4
Note
(1) A label has been placed over the upper surface of the SYSMAC LINK Unit
to prevent wire cuttings from entering the Unit. When wiring the backup
power supply, leave the label in place.
(2) When wiring is complete, remove the label to avoid overheating.
(3) Use a power supply that is not connected to PLC operation, as in the case
of the node bypass function, for the backup power supply so that when
the power to the PLC is turned OFF, the backup power supply will contin-
ue.
(4) Use a dedicated power supply for the backup power supply. Do not share
a power supply being used for I/O, motors, or control systems.
(5) When two or more nodes are connected to a single backup power supply,
wire each node separately.
Note
Unlike the CV500-SLK11, the CS1W-SLK11 does not require an Auxiliary
Power Supply Unit for the node bypass function. Instead, directly connect a
24-VDC external power source as a backup power supply.
Attach crimp terminals to the power supply cable when connecting the backup
power supply to the SYSMAC LINK Unit.
Crimp Terminals
Use an M3 crimp terminal, as illustrated below.
Current consumption
200 mA max. at 24 V DC (per node)
Inrush current
2.5 A max. (24 V DC, 5-ms rise time)
Item
Specification
Backup power
supply
Backup power
supply
OK
Wrong
Backup
power
supply
24 VDC
6.2 mm max.
6.2 mm max.
Содержание CS1W-SLK11-21 - 06-2004
Страница 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Страница 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ......
Страница 11: ......
Страница 17: ......
Страница 49: ......
Страница 107: ......
Страница 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Страница 143: ......
Страница 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Страница 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Страница 177: ......
Страница 179: ......
Страница 195: ......
Страница 199: ......
Страница 201: ...Authorized Distributor Cat No W367 E1 02 Note Specifications subject to change without notice Printed in Japan...
Страница 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...