CX-Programmer Procedures
Section 4-12
2.
Select
SYSMAC LINK Data Link Table
and then click the
OK
button. The
Data Link Editor [SYSMAC LINK] will start.
3.
Set the data link communications cycle time in the Cycle Time field under
Common Link
. If you select
Auto
, the optimum communications cycle time
will be automatically calculated according to the data link tables. If you se-
lect
Manual
, set the time manually between 5 to 255 ms (refer to
4-11 Data
Link Characteristics
for communications cycle time details).
4.
Double click a
node address in the Nodes field, or select
Table
and then
Edit Table Item
. The Data Link Table Entry Dialog Box will appear.
Note
(a) If using CX-Programmer Ver. 1.2 (Service Pack 1), select CV/
CVM1 for the PLC type when using a CS-series SYSMAC LINK
Unit.
If a CV/CVM1 PLC is set, the manual settings words will be limit-
ed to the same words as for CVM1/CV, as follows:
CIO Area: CIO 0000 to CIO 2555
DM Area: D00000 to D24575
(b) CS-series PLC types can be specified with CX-Programmer Ver.
2.0 or later and so the above limitations to manual settings words
do not apply.
Содержание CS1W-SLK11-21 - 06-2004
Страница 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Страница 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ......
Страница 11: ......
Страница 17: ......
Страница 49: ......
Страница 107: ......
Страница 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Страница 143: ......
Страница 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Страница 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Страница 177: ......
Страница 179: ......
Страница 195: ......
Страница 199: ......
Страница 201: ...Authorized Distributor Cat No W367 E1 02 Note Specifications subject to change without notice Printed in Japan...
Страница 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...