5.8
Information
BU 0500 GB
Subject to technical alterations
119
Parameter
Set value / Description / Note
Device
Supervisor
Parameter
set
P741
... - 01
...
... - 13
Bus Out process data
S
... - 01 =
Status Word
Status word, source from P509.
... - 02 =
Actual value 1 (P543)
... - 03 =
Actual value 2 (P544)
... - 04 =
Actual value 3 (P545)
... - 05 =
Bus I/O Out Bit (P481)
The displayed value depicts
all Bus Out Bit sources linked
with OR.
... - 06 =
Parameter data Out 1
... - 07 =
Parameter data Out 2
... - 08 =
Parameter data Out 3
... - 09 =
Parameter data Out 4
... - 10 =
Parameter data Out 5
Data during parameter
transfer.
0000 ... FFFF (hex)
This parameter informs
about the actual status
word and the actual
values that are
transferred via the bus
systems.
... - 11 =
Actual value 1 leading function
... - 12 =
Actual value 2 leading function
... - 13 =
Actual value 3 leading function
Actual value of leading
function P502/P503.
P742 Database
version
S
0 ... 9999
Displays the internal database version of the FI.
P743 Inverter
type
0.25 ... 11.00
Displays the inverter output in kW, e.g. "1.50"
⇒
FI with 1.5kW Nominal power.
P744 Configuration
level
This parameter displays the special devices integrated in the FI. Display is in hexadecimal code
(SimpleBox, ControlBox, Bus system).
The display is in plain text when the ParameterBox is used.
0000 ... FFFF (hex)
SK 500E/510E = 0000
SK 520E = 0101
SK 530E = 0201
P745 Module
version
0.0 ... 999.9
Design status (software version) of the technology unit (SK TU3-xxx), but only when own
processor is present, therefore not for SK TU3-CTR.
Have this data ready if you have a technical query.
P746 Module
status
S
0000 ... FFFF (hex)
Actual status (readiness, error, communication) of the technology unit (SK TU3-xxx), but only
when own processor is present, therefore not for SK TU3-CTR.
Code details can be found in the respective BUS module manual. Different contents are shown
depending on the modules.
P747
Inverter voltage range
Indicates the mains voltage range for which this device is specified.
0 ... 2
0 =
100..0.120V
1 =
200..0.240V
2 =
380...480V