5.5 Control terminals
BU 0500 GB
Subject to technical alterations
99
Parameter
Set value / Description / Note
Device
Supervisor
Parameter
set
14 =
... 29 reserved (excluding 18)
---
30 =
Bus IO In Bit 0 / Bus In Bit 0 *
Closes
31 =
Bus IO In Bit 1 / Bus In Bit 1 *
Closes
32 =
Bus IO In Bit 2 / Bus In Bit 2 *
Closes
33 =
Bus IO In Bit 3 / Bus In Bit 3 *
Closes
34 =
Bus IO In Bit 4 / Bus In Bit 4 *
Closes
35 =
Bus IO In Bit 5 / Bus In Bit 5 *
Closes
36 =
Bus IO In Bit 6 / Bus In Bit 6 *
Closes
37 =
Bus IO In Bit 7 / Bus In Bit 7 *
Closes
38 =
Value from Bus setpoint *
Closes
*) P546...P548 = 17 or 19
P435
Standardisation output 1
P
-400 ... 400 %
[ 100 ]
Adjustment of the limit values of the relay function. For a negative value, the output function will
be output negative.
Reference to the following values:
Current limit (3) = x [%]
⋅
P203 >Motor nominal current<
Torque current limit (4) = x [%]
⋅
P203
⋅
P206 (calculated nominal motor torque)
Frequency limit (5) = x [%]
⋅
P201 >Nominal motor frequency<
P436
Hysteresis output 1
S P
1 ... 100 %
[ 10 ]
Difference between switch-on and switch-off point to prevent oscillation of the output signal.
P441
Function output 2 (K2)
P
0 ... 38
[ 7 ]
Control terminals 3/4:
Functions are identical to P434!
P442
Standardisation output 2
P
-400 ... 400 %
[ 100 ]
Functions are identical to P435!
P443
Hysteresis output 2
S P
1 ... 100 %
[ 10 ]
Functions are identical to P436!
P450
Function output 3 (DOUT1)
SK 520E
and above
P
0 ... 38
[ 0 ]
Control terminals 5/40:
Functions are identical to P434! Digital output, 15V to DGND.
P451
Standardisation output 3
SK 520E
and above
P
-400 ... 400 %
[ 100 ]
Functions are identical to P435!
P452
Hysteresis output 3
SK 520E
and above
S P
1 ... 100 %
[ 10 ]
Functions are identical to P436!
F
urther detai
ls in the BUS
manu
als