NORDAC SK 5xxE Manual
110
Subject to technical alterations
BU 0500 GB
Parameter
Set value / Description / Note
Device
Supervisor
Parameter
set
P542
Set analog output
S
0.0 ... 10.0 V
[ 0.0 ]
The analog output of the FI can be set with this function, independently of the actual operating state.
To do this, the relevant analog output must be set to the function "External control" (P418 = 7).
This function can either be used manually or in combination with a bus control. The value set here
will, once confirmed, be produced at the analog output.
P543
Actual bus value 1
S P
The return value 1 can be selected for bus actuation in this parameter.
NOTE:
Further details can be found in the respective BUS operating instructions or in the
description of P418.
0 ... 22
[ 1 ]
0 =
Off
1 =
Actual frequency
2 =
Actual speed
3 =
Current
4 =
Torque current (100% = P112)
5 =
State of digital inputs and outputs
1
6 =
… 7 reserved
8 =
Setpoint frequency
9 =
Error number
10 =
… 11 reserved
12 =
Bus IO Out Bits 0...7
13 =
… 16 reserved
17 =
Value analog input 1 (P400)
18 =
Value analog input 2 (P405)
19 =
Desired frequency master value (P503)
20 =
Desired frequency after master value
ramp
21 =
Actual frequency without master value slip
22 =
Speed l from encoder (only possible with
SK 52x/53xE and encoder feedback)
P544
Actual bus value 2
S P
0 ... 22
[ 0 ]
This parameter is identical to P543.
Condition is PPO 2 or PPO 4 type (P507).
P545
Actual bus value 3
S P
0 ... 22
[ 0 ]
This parameter is identical to P543.
Condition is PPO 2 or PPO 4 type (P507).
1
The assignment of the dig. inputs in P543/ 544/ 545 = 5
Bit 0 = DigIn 1
Bit 1 = DigIn 2
Bit 2 = DigIn 3
Bit 3 = DigIn 4
Bit 4 = DigIn 5
Bit 5 = DigIn 6 (SK 520/530E) Bit 6 = DigIn 7 (SK 52x/53xE)
Bit 7 = reserved
Bit 8 = reserved
Bit 9 = reserved
Bit 10 = reserved
Bit 11 = reserved
Bit 12 = Out 1
Bit 13 = Out 2
Bit 14 = Out 3 (SK 52x/53xE)
Bit 15 = Out 4 (SK 52x/53xE)