NORDAC SK 5xxE Manual
58
Subject to technical alterations
BU 0500 GB
Parameter
Set value / Description / Note
P1306
Box password
If the >Password< function is to be reset, the password selected in the >Set Password<
parameter must be entered here. If the correct password is selected, all of the ParameterBox
functions and the parameters of the connected frequency inverter can be used again.
NOTE:
With the master-password ‘65’ the current password is displayed and can be confirmed
with the ENTER key.
P1307
Reset Box parameter
In this parameter the ParameterBox can be reset to the default setting. All ParameterBox
settings and the data in the storage media will be deleted.
P1308
Software version
Displays the software version of the ParameterBox (NORDAC
p-box
). Please keep for future
use.
3.2.5 ParameterBox error messages
Display
Error
Cause
¾
Remedy
Communication
error
200
INCORRECT PARAMETER NUMBER
201
PARAMETER VALUE CANNOT BE
CHANGED
202
PARAMETER OUTSIDE VALUE
RANGE
203
FAULTY SUB INDEX
204
NO ARRAY PARAMETERS
205
WRONG PARAMETER TYPE
206
INCORRECT RESPONSE
RECOGNITION USS INTERFACE
These error messages are due to EMC interferences or differing software
versions of the participants.
¾
Check the software version of the ParameterBox and that of the connected
frequency inverter.
¾
Check the cabling of all components, regarding possible EMC interference
207
USS INTERFACE CHECKSUM
FAULT
Communication between frequency inverter and ParameterBox is faulty (EMC),
safe operation cannot be guaranteed.
¾
Check the connection to the frequency inverter. Use a shielded cable
between the devices. Route the BUS leads separately from the motor cables.
208
FAULTY STATUS RECOGNITION
USS INTERFACE
Communication between frequency inverter and ParameterBox is faulty (EMC),
safe operation cannot be guaranteed.
¾
Check the connection to the frequency inverter. Use a shielded cable
between the devices. Route the BUS leads separately from the motor cables.
209_1
INVERTER DOES NOT RESPOND
The ParameterBox is waiting for a response from the connected frequency
inverter. The waiting time has elapsed without a response being received.
¾
Check the connection to the frequency inverter. The settings of the USS
parameters for the frequency inverter were changed during operation.