5.6
Additional parameters
BU 0500 GB
Subject to technical alterations
111
Parameter
Set value / Description / Note
Device
Supervisor
Parameter
set
P546
Bus setpoint 1
S P
In this parameter, a function is allocated to the output setpoint 1 during bus actuation.
NOTE:
Further details can be found in the respective BUS operating instructions or in the
description of P400.
0 ... 47
[ 1 ]
0 =
Off
1 =
Setpoint frequency (16 Bit)
2 =
Torque current limit (P112)
3 =
Actual frequency PID
4 =
Frequency addition
5 =
Frequency subtraction
6 =
Current limit (P536)
7 =
Maximum frequency (P105)
8 =
Actual PID frequency limited
9 =
Actual PID frequency monitored
10 =
Torque servo mode (P300)
11 =
Torque precontrol (P214)
12 =
reserved
13 =
Multiplication
14 =
PI process controller actual value
15 =
PI process controller setpoint
16 =
PI process controller lead
17 =
Bus In Bits 0...7
18 =
reserved
19 =
Status output (P434/441/450/455=38)
20 =
Value analog output (P418=31)
21 =
…45 reserved for SK 530E
Æ
BU 0510
46 =
Setpoint torque process controller
47 =
reserved
P547
Bus setpoint 2
S P
0 ... 47
[ 0 ]
This parameter is identical to P546.
P548
Bus setpoint 3
S P
0 ... 47
[ 0 ]
This parameter is identical to P546.
P549 PotentiometerBox
function
S
In this parameter, the setpoint of the PotentiometerBox (SK TU3-POT) is assigned with a function.
(An explanation can be found in the description of P400)
0 ... 16
[ 0 ]
0 =
Off
1 =
Setpoint frequency
2 =
Torque current limit
3 =
Actual frequency PID
4 =
Frequency addition
5 =
Frequency subtraction
6 =
Current limit
7 =
Maximum frequency
8 =
Actual PID frequency limited
9 =
Actual PID frequency monitored
10 =
Torque
11 =
Torque precontrol
12 =
reserved
13 =
Multiplication
14 =
PI process controller actual value
15 =
PI process controller setpoint
16 =
PI process controller lead
Controlling the FI with the SK CSX-0:
If P549=1 is set and the operating value display P000 is
selected, the drive can be controlled with the SimpleBox (see Section 3.2.1) on the FI.
Depressing the button for a long time starts the drive, pressing briefly stops it. The speed of
rotation can be controlled in the positive and negative range by means of the rotating knob.
Control of the FI with the SimpleBox is not possible in combination with the ParameterBox SK
TU3-PAR.
NOTE:
Please note that in this operating mode the drive can only be stopped with the
button in the operating value display (brief press) or by switching off the mains
supply.