5.7 Positioning
The parameter group P6xx is only included in SK 530E frequency inverters. These are used to set the
positioning control of the SK 530E
A detailed description of these parameters can be found in manual BU 0510. (www.nord.com)
5.8 Information
Parameter
Set value / Description / Note
Device
Supervisor
Parameter
set
P700 Current
fault
0.0 ... 21.4
Current pending fault. Further details in Section 6 Error messages.
SimpleBox/ControlBox:
Descriptions of the individual error numbers can be found in the point
Error messages.
ParameterBox:
Errors are displayed in plain text, further information can be found in the point
Error messages.
P701
... - 01
...
... - 05
Last fault 1...5
0.0 ... 21.4
This parameter stores the last 5 faults. Further details in Section 6 Error messages.
The ControlBox must be used to select the corresponding memory location 1...5- (Array
parameter), and confirmed using the ENTER key to read the stored error code.
P702
... - 01
...
... - 05
Freq. previous fault 1...5
S
-400.0 ... 400.0 Hz
This parameter stores the output frequency that was being delivered at the time the fault
occurred. The values of the last 5 faults are stored.
The ControlBox must be used to select the corresponding memory location 1...5- (Array
parameter), and confirmed using the ENTER key to read the stored error code.
P703
... - 01
...
... - 05
Current previous fault 1...5
S
0.0 ... 999.9 A
This parameter stores the output current that was being delivered at the time the fault occurred.
The values of the last 5 errors are stored.
The ControlBox must be used to select the corresponding memory location 1...5- (Array
parameter), and confirmed using the ENTER key to read the stored error code.
P704
... - 01
...
... - 05
Voltage previous fault 1...5
S
0 ... 500 V AC
This parameter stores the output voltage that was being delivered at the time the fault occurred.
The values of the last 5 faults are stored.
The ControlBox must be used to select the corresponding memory location 1...5- (Array
parameter), and confirmed using the ENTER key to read the stored error code.