INVALID PASSWORD
Attempt to alter a parameter without a valid Box password being entered in
parameter >Box Password< P 1306.
232
BUS SCAN ONLY WHEN IN ONLINE
MODE ONLINE
A bus scan (search for a connected frequency inverter) is only possible when in
ONLINE mode.
Warnings
240
OVERWRITE DATA?
Æ
YES
NO
241
DELETE DATA?
Æ
YES
NO
242
MOVE SW VERSION?
Æ
CONTINUE
CANCEL
243
MOVE SERIES?
Æ
CONTINUE
CANCEL
244
DELETE ALL DATA?
Æ
YES
NO
These warnings indicate that there is a possibly significant change which needs
additional confirmation.
Once the next procedure has been selected, it must be confirmed with the
"ENTER" key.
Inverter control error
250
THIS FUNCTION IS NOT ENABLED
The required function is not enabled in the parameter >Interface< of the
frequency inverter.
¾
Change the value of the parameter >Interface< of the connected inverter to
the required function. More detailed information can be obtained from the
operating instructions for the frequency inverter.
251
CONTROL COMMAND WAS NOT
SUCCESSFUL
The control command cannot be implemented by the frequency inverter, as a
higher priority function, e.g. Quick stop or an OFF signal to the control terminals
of the frequency inverter is present.
252
CONTROL OFFLINE NOT POSSIBLE
Call up of a control function in Offline mode.
¾
Change the operating mode of the ParameterBox in the parameter
>Operating Mode< P1302 to Online and repeat the action.
253
ERROR ACKNOWLEDGEMENT NOT
SUCCESSFUL
The acknowledgement of an error at the frequency inverter was not successful,
the error message remains.
Error message from inverter
“ERROR No. FROM INVERTER”
INVERTER FAULT "INVERTER
FAULT TEXT"
A fault has occurred in the inverter with the number displayed. The inverter error
number and text are displayed.