2 Mounting and installation
BU 0200 en-US-4920
75
Pos : 170 /Anleit ungen/El ektr onik /FU und St art er/2. M ontage und I nst allation/ Elek trischer Ans chl uss/Dr ehg eber/F arb- und Kontak tbeleg ung für Inkr ement al drehgeber (HT L) [ SK 2x xE] @ 19\m od_1511782908220_14638. docx @ 2372927 @ 2 @ 1
2.5 Color and contact assignments for the incremental encoder (HTL)
Function
Wire colors,
for incremental encoder
1)
Assignment for SK 2xxE
24V supply
brown/green
43 (/44)
24V (VO)
0V supply
white/green
40
0V (GND)
Track A
brown
22
DIN2
Track A inverse (A /)
green
--
Track B
gray
23
DIN3
Track B inverse (B /)
pink
--
Track 0
red
21
DIN1
Track 0 inverse
black
--
Cable shield
Large-area connection to variable frequency drive housing.
1)
Wire colors depend on the type of encoder and may differ. Please
note
the encoder
data sheet
!
Note the current consumption of the encoder (normally up to 150 mA) and the permissible load on the
voltage source.
Only digital inputs DIN 2 and DIN 3 are in a position to process the signals of an HTL encoder. To use
an encoder, activate parameters (P300) and/or (P600) according to requirements (speed
feedback/servo mode or positioning).
Pos : 171 /Anleit ungen/El ektr onik /FU und St art er/1. Allgemei nes /Sic herheits- und Ins tall ations hinw eis e und W arn- Gefahrenhinw eise/neu/War n- und Gefahrenhinw eise/I nf ormati on - Doppel bel egung DIN 2 und DIN 3 [SK 2xx E] @ 19\mod_1511860681545_14638.docx @ 2373600 @ @ 1
Information
DIN 2 and DIN 3 double allocation
Digital inputs DIN2 and DIN3 are used for 2 different functions:
1. for digital functions that can be parameterized (e.g. “enable left”),
2. for evaluation of an incremental encoder.
Both functions are coupled by an OR link.
Evaluation of an incremental encoder is always activated. This means that when an incremental encoder is
connected, make sure that the digital functions are switched off (parameter (P420 [-02] and [-03]) or with DIP
switch (chapter 4.3.2.2)).
Pos : 172 /Anleit ungen/El ektr onik /FU und St art er/1. Allgemei nes /Sic herheits- und Ins tall ations hinw eis e und W arn- Gefahrenhinw eise/neu/War n- und Gefahrenhinw eise/I nf ormati on - Drehrichtung bzw Stör ung des Gebersignals (Drehg eber) [ SK 2xxE, SK 2xx E-FDS, + ?] @ 19\mod_1511860695438_14638.docx @ 2373636 @ @ 1
Information
Rotation direction
The "counting direction" of the incremental encoder must correspond to the direction of rotation of the motor. If the
two directions are not identical, the connections of the encoder tracks (track A and track B) must be switched.
Alternatively, the resolution (line number) of the encoder can be set with a negative prefix in the
P301
parameter.
Information
Encoder signal faults
Wires that are not required (e.g. track A inverse/B inverse) must be insulated.
Otherwise, if these wires come into contact with each other or the cable shield, short circuits can occur that can
cause encoder signal problems or destruction of the encoder.
Pos : 173 /Anleit ungen/El ektr onik /FU und St art er/2. M ontage und I nst allation/ Elek trischer Ans chl uss/Dr ehg eber/F arb- und Kontak tbeleg ung für Inkr ement al drehgeber (HT L)_Ergänzung [ SK 2xx E] @ 11\m od_1458311618705_14638. docx @ 314438 @ @ 1
If the rotary encoder has a zero track, connect this to digital input 1 of the device. The zero track is
read out by the variable frequency drive if parameter P420 [-01] has been set to function 43.
Pos : 174 /Allgem ein/ Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0. doc x @ 2265496 @ @ 1
Содержание NORDAC FLEX SK 2 E-111-123-A Series
Страница 1: ...BU 0200 en US NORDAC FLEX SK 200E SK 235E Users Manual for Frequency Inverters...
Страница 5: ...Publisher BU 0200 en US 4920 5...
Страница 283: ...Key word index BU 0200 en US 4920 283...
Страница 284: ...6072003 4920...