5 Parameter
BU 0200 en-US-4920
207
P558
Flux delay
(magnetization time)
S
P
0 / 1 / 2 ... 5000 ms
{ 1 }
The ISD control can only function correctly if there is a magnetic field in the motor. For this
reason, a DC current is applied before starting the motor to provide the excitation of the stator
winding. The duration depends on the size of the motor and is automatically set in the factory
setting of the VFD.
For time-critical applications, the magnetizing time can be set or deactivated.
0 =
Disabled
1 =
Automatic calculation
2 ... 5000 =
Time set in [ms]
NOTE:
Setting values that are too low can reduce the dynamics and starting torque.
Pos : 560 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P559 – DC-Nac hlauf zeit @ 0\m od_1328098856657_14638.docx @ 15099 @ @ 1
P559
DC Run-on time
(DC run-on time)
S
P
0.00 ... 30.00 s
{ 0.50 }
Following a stop signal and the braking ramp, a direct current is briefly applied to the motor to
fully bring the drive to a stop. Depending on the inertia, the time for which the current is applied
can be set in this parameter.
The current level depends on the previous braking procedure (current vector control) or the static
boost (linear characteristic).
Pos : 561 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P560 – Param et er Speichermode @ 0\mod_1328098918376_14638. doc x @ 15100 @ @ 1
P560
Mode of parameter save
(parameter saving mode)
S
0 ... 2
{ 1 }
0 =
RAM only
, changes to the parameter settings are no longer saved on the EEPROM. All
previously saved settings are retained, even if the VFD is disconnected from the power.
1 =
RAM and EEPROM
, all parameter changes are automatically written to the EEPROM
and remain stored there even if the VFD is disconnected from the power supply.
2 =
OFF
, no saving in RAM and EEPROM possible (no parameter changes are accepted)
NOTE:
If BUS communication is used to implement parameter changes, it must be ensured
that the maximum number of write cycles (100,000 x) in the EEPROM is not
exceeded.
Pos : 562 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P560 – Param et er Speichermode_Ergänzung_01 [ SK 2x xE, SK 2xx E-FDS] @ 10\m od_1456908913923_14638. docx @ 311260 @ @ 1
PLC:
A stored PLC program is also protected by the settings "
0
" or "
2
". However,
with the setting "0" the PLC program can also not be loaded or executed.
Pos : 563 /Allgem ein/ Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0. doc x @ 2265496 @ @ 1
Содержание NORDAC FLEX SK 2 E-111-123-A Series
Страница 1: ...BU 0200 en US NORDAC FLEX SK 200E SK 235E Users Manual for Frequency Inverters...
Страница 5: ...Publisher BU 0200 en US 4920 5...
Страница 283: ...Key word index BU 0200 en US 4920 283...
Страница 284: ...6072003 4920...